| Plan Review Notes For Permit 14100698 |
| Permit Number |
14100698 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-23 14:33:46 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | A LIFE SAFETY PLAN WAS NOT INCLUDED WITH THE SUBMITTAL. | | | THE LIFE SAFETY PLAN SHALL INCLUDE, BUT NOT LIMITED TO, | | | THE PROPOSED OCCUPANCY LOAD, ALL EXIT PATHS, EXIT | | | SIGNS, EXITS, EMERGENCY LIGHTS, COMMON PATHS OF TRAVEL, | | | TRAVEL DISTANCES, FIRE EXTINGUISHER LOCATIONS. | | | | | | SHEET A - 04 INDICATED A WALL ENCROACHMENT INTO THE | | | HALLWAY AT THE EXECUTIVE OFFICE 367, LOCATION. THE | | | REDUCED HALL DIMENSION IS NOT INDICATED AND THE REDUCED | | | HALL IS NOT APPROVED. IT IS RECOMMENDED THAT THE WALL | | | BE MOVED INTO THE ROOM TO MAINTAIN THE HALLWAY | | | DIMENSION(AS HAND DRAWN ON ONE OF THE SHEETS). | | | | | | SHEET A - 04, THE DOOR TO CLOSET 345 INDICATES IT | | | SWINGS IN TO CORRIDOR. THE DOOR CAN NOT SWING INTO MORE | | | THAN 1/2 THE CORRIDOR WIDTH AND IS NOT APPROVED. | | | | | | SHEET A - 01, INDICATES THAT A FIRE ALARM WILL BE | | | INSTALLED; HOWEVER, NO FIRE ALARM PLANS ARE INCLUDED. | | | AN ENGINEERED FIRE ALARM PLAN SHALL BE SUBMITTED WITH | | | THIS PLAN AND SHOP DRAWINGS SUBMITTED BY THE INSTALLING | | | CONTRACTOR. |
|