| Plan Review Notes For Permit 14100698 |
| Permit Number |
14100698 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-24 09:57:04 | 10/24/2014 | | | PROJECT: INTERIOR BUILDOUT. SUITE 1400 | | | PERMIT#: 14100698 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1) INDICATE LOCATIONS FOR ELECTRICAL SERVICE AND | | | PANELBOARDS ILLUSTRATED ON SINGLE LINE RISER DIAGRAM ON | | | SHEETE3.1. | | | | | | 2) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR | | | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC | | | 110.16, 110.22 | | | | | | 3) A SEPARATE SUBMITTAL WITH SHOP DRAWINGS AND PRODUCT | | | DATA SHEETS FOR ACCESS CONTROL AND FIRE ALARM SYSTEMS. | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | | | | | | | |
|