| 2014-11-17 12:28:54 | BUILDING PLAN REVIEW |
| | PERMIT: 1410069 |
| | ADD: 222 LAKEVIEW SUITE # 300 |
| | CONT: GREEN CONSTRUCTION |
| | TEL: (305) 670-1000 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. NOV. 17/2014 |
| | ACTION: DENIED |
| | |
| | NOTICE: THE PERMIT APPLICATION UNDER DISCREPTION OF |
| | WORK: TYPED SUITE 300/ HAND WRITTEN 1ST FLOOR BUILD |
| | OUT, THIS REVIEW WILL BE FORE A 3RD FLOOR BUILDOUT AS |
| | STATED ON PLANS. |
| | |
| | |
| | 1) SHEET A-04: |
| | !A) IT ROOM # 345 PLEASE PROVIDE WHAT THE CLEAR |
| | UNOBSTRUCKED SWING OF THE DOOR? SHOW COMPLIANCE WITH |
| | 2010 FBC-B 1008.1.9.11 DURING ITS SWING, ANY DOOR IN A |
| | MEANS OF EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST ONE |
| | HALF OF THE REQUIRED WIDTH OF A CORRIDOR, PASSAGEWAY, |
| | NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE |
| | REQUIRED WIDTH OF A CORRIDOR OR PASSAGEWAY, WHEN FULLY |
| | OPEN. |
| | |
| | 1B) THE EXECUTIVE OFFICE # 367 THE CORRIDOR DOES NOT |
| | PROVIDE WHAT THE REDUCED WIDTH IS IN THE NEW OFFICESITE |
| | THAT IS PROVIDED. COORIDORS WITH OCCUPANT LOADS GREATER |
| | THAN 44 INCHES, 2010 FBC-B 1018.2 . |
| | |
| | 1C)(1) PRIVATE RESTROOM # 355 PLEASE PROVIDE COMPLIANCE |
| | WITH 2010 FBC-ACCESSIBILITY CODE 213.2 TOILET ROOMS AND |
| | BATHING ROOMS. WHERE TOILET ROOMS ARE PROVIDED, EACH |
| | TOILET ROOM SHALL COMPLY WITH 603. 603.2.1 TURNING |
| | SPACE. TURNING SPACE COMPLYING WITH 304 SHALL BE |
| | PROVIDED WITHIN THE ROOM. |
| | |
| | 1C)(2) PLEASE SHOW COMPLIANCE ALSO WITH ACCESS. CODE |
| | 604.3.2 OVERLAP. THE REQUIRED CLEARANCE AROUND THE |
| | WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER |
| | CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY |
| | NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE |
| | ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT |
| | OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER |
| | FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE |
| | REQUIRED WATER CLOSET CLEARANCE. |
| | |
| | 1C)(3) THE PLANS DO NOT PROVIDE DETAILS FOR BACKING |
| | 2010 FBC- ACCESS. CODE 609. |
| | |
| | 1C)(4) IF A INSWING DOOR IS TO BE INSTALLED PLEASE SHOW |
| | COMPLYANCE WITH ACCESS. CODE 603.2.3 DOOR SWING. ECEP. |
| | # 2 WHERE THE TOILET ROOM OR BATHING ROOM IS FOR |
| | INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING WITH |
| | 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE |
| | DOOR SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE |
| | CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY |
| | FIXTURE. |
| | |
| | 1D) SHEET A-04 BOTH KITCHENETTES 336 & 350 APPEAR TO BE |
| | MISMARKED DETAIL IS SHOWN AS DETAIL # 3/ A-09 WHERE AS |
| | SHEET A-07.5 SHOWS THE CORRECT DETAIL. DISCREPANCY IN |
| | PLANS. 107.2.1.3. |
| | |
| | 1E) THE (2) NEW ELEVATORS THAT ARE NOT PART OF THIS |
| | CONTRACT WILL EFFECT THE OUTCOME OF THIS PROJECT, |
| | PLEASE INDICATE HOW COMPLIANCE WITH FBC-B 708.14.1 |
| | ELEVATOR LOBBIES OR A EXCEPTION WILL BE COMPLIED WITH. |
| | |
| | 2) SHEET A-07.6 DETAIL 6 SHOWS A RAMP AND RAISED |
| | PLATFORM. NOTE THIS IS A HIGH-RISE AND MUST MEET |
| | COMPLIANCE WITH 2010 FBC-B 603.1. 410.4 PLATFORM |
| | CONSTRUCTION. |
| | PERMANENT PLATFORMS SHALL BE CONSTRUCTED OF MATERIALS |
| | AS REQUIRED FOR THE TYPE OF CONSTRUCTION OF THE |
| | BUILDING IN WHICH THE PERMANENT PLATFORM IS LOCATED. |
| | PERMANENT PLATFORMS ARE PERMITTED TO BE CONSTRUCTED OF |
| | FIRE-RETARDANT-TREATED WOOD FOR TYPES I, II AND IV |
| | CONSTRUCTION. |
| | |
| | TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA |
| | TUS.ASPX FOR PERMIT STATUS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |