| 2015-03-03 11:40:57 | 3/3/2015 |
| | PROJECT: MARATHON SIGN |
| | PERMIT#: 14100684 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION. |
| | |
| | 1) NEC 600.3 AND 11O.3(B) |
| | ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING ? |
| | FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND |
| | INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS |
| | OTHERWISE APPROVED BY SPECIAL PERMISSION. PROVIDE THE |
| | LISTING INFORMATION FOR THE SIGN AS A WHOLE AND FOR THE |
| | DRIVERS TO BE INSTALLED FOR OPERATION OF THE LED'S |
| | |
| | 2) NEC 600.6(A)(1) |
| | EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER |
| | CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE |
| | LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY |
| | OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL |
| | UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN OR |
| | OUTLINE LIGHTING SYSTEM THAT IT CONTROLS. INDICATE OM |
| | THE PLANS WHERE AND HOW THE PROPOSED INSTALLATION WILL |
| | CONFORM TO THE NEC 600.6 |
| | |
| | 3) FBC-E 505.2.4 |
| | ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL |
| | HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN |
| | NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME |
| | CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES |
| | SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS |
| | OF POWER FOR A MINIMUM OF 10 HOURS. INDICATE ON THE |
| | PLAN HOW THE COMPLETED INSTALLATION WILL COMPLY WITH |
| | THE FBC-E 505.2. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |