| Plan Review Notes For Permit 14100679 |
| Permit Number |
14100679 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-11-14 11:42:56 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THERE IS INSUFFICIENT DETAIL TO DETERMINE AN APPROVAL | | | FOR AN OCCUPANCY CHANGE. | | | | | | EDUCATIONAL GALLERY GROUP IS INDICATED ON THE THE | | | SECOND SHEET. INFOMATION SHALL BE PROVIDED AS TO THE | | | INTENT OF THIS OCCUPANCY. ARE CLASSROOM SPACES | | | PROPOSED? WILL IT BE AN ASSEMBLY SPACE WHERE PEOPLE | | | VISIT AND WALK AROUND, HOLD GROUP EVENTS, ETC.? | | | | | | WILL THERE BE ALTERATIONS TO THE FLOOR PLAN, HALF | | | WALLS, ISLE SEPARATIONS, TABLES, CHAIRS, AND/OR | | | ANYTHING THAT WILL BE ADDED THANT MAY ALTER EXIT | | | ABILITY OR PATRONS? | | | | | | IS THE LOFT ENCLOSED, DOES IT HAVE A RAILING ALONG THE | | | PERIMETER, OR WINDOWS? | | | | | | ONLY ONE DOOR IS INDICATED ON THE PLAN. BASED ON THE | | | INFORMATION PROVIDED AND A SECOND EXIT DOOR IS | | | REQUIRED. | | | | | | A LIFE SAFETY PLAN SHALL BE SUBMITTED INCLUDING | | | OCCUPANCY LOADS FOR EACH SPACE, EXIT PATHS, EMERGENCY | | | LIGHTING, EXIT DOORS, EXITS DISCHARGES, AND FIRE | | | EXTINGUISHER LOCATIONS |
|