| 2014-11-07 18:37:38 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | MECHANICAL - NO MECHANICAL WORK IS SHOWN ON THE PLANS |
| | OTHER THAN BATH AND DRYER EXHAUST. HOWEVER, THE PANEL |
| | SCHEDULE ON THE ELECTRICAL PLAN INDICATES THERE IS |
| | AIR-CONDITIONING. |
| | |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION |
| | SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER |
| | CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS |
| | 402 OR 405. |
| | FBC ENERGY CONSERVATION - SECT. 103.2.3.2 CODE |
| | COMPLIANCE CERTIFICATION. |
| | THE BUILDING?S OWNER, THE OWNER?S ARCHITECT, OR OTHER |
| | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE |
| | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR |
| | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| | RENOVATION. |
| | |
| | |
| | 2) FBC-R - M1401.3 SIZING. HEATING AND COOLING |
| | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS |
| | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER |
| | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. |
| | PROVIDE EQUIPMENT SIZING CALCULATIONS. FBC ENERGY |
| | CONSERVATION - SECT. 403.6.1 EQUIPMENT SIZING. |
| | HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN |
| | ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| | LOADS CALCULATED IN ACCORDANCE WITH MANUAL J OR OTHER |
| | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES, |
| | BASED ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION |
| | OF THE BUILDING. THE MANUFACTURER AND MODEL NUMBER OF |
| | THE OUTDOOR AND INDOOR UNITS (IF SPLIT SYSTEM) SHALL BE |
| | SUBMITTED ALONG WITH THE SENSIBLE AND TOTAL COOLING |
| | CAPACITIES AT THE DESIGN CONDITIONS DESCRIBED IN |
| | SECTION 302.1. THIS CODE DOES NOT ALLOW DESIGNER SAFETY |
| | FACTORS, PROVISIONS FOR FUTURE EXPANSION OR OTHER |
| | FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM SIZING |
| | CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY LOCAL |
| | INTERMITTENT MECHANICAL VENTILATION SUCH AS STANDARD |
| | KITCHEN AND BATHROOM EXHAUST SYSTEMS. |
| | |
| | 3) FBC - 107.3.5.3 PROVIDE A MECHANICAL PLAN TO SHOW |
| | LOCATION AND SIZES OF ALL DUCTS, SUPPLY & RETURN |
| | GRILLS, CFMS AT EACH OUTLET. PROVIDE AN EQUIPMENT |
| | SCHEDULE ON THE MECHANICAL PLANS THAT CORRESPONDS WITH |
| | THE SIZING CALCULATIONS. FBC -107.3.5.1.4 MECHANICAL |
| | MINIMUM PLAN REVIEW CRITERIA: SHOW, EXHAUST SYSTEMS, |
| | CLOTHES DRYER EXHAUST, KITCHEN EQUIPMENT EXHAUST, |
| | SPECIALTY EXHAUST SYSTEMS, EQUIPMENT, EQUIPMENT |
| | LOCATION, MAKE-UP AIR, ROOF-MOUNTED EQUIPMENT, DUCT |
| | SYSTEMS, VENTILATION, COMBUSTION AIR, CHIMNEYS, |
| | FIREPLACES AND VENTS, APPLIANCES, BOILERS, |
| | REFRIGERATION, BATHROOM VENTILATION, LABORATORY, DESIGN |
| | FLOOD ELEVATION. |
| | |
| | 4) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT |
| | BEDROOMS. |
| | |
| | 5) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | |
| | |
| | |