Plan Review Notes For Permit 14100673
Permit Number 14100673
Review Stop E
Sequence Number 1
Notes
Date Text
2014-11-08 09:22:2911/8/2014
 PROJECT: 901 FOREST HILL
 PERMIT#: 14100673
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) CLARIFICATION REQUIRED. PLEASE PROVIDE ADDITIONAL
 INFORMATION ON THE FOLLOWING:
 A) THE SIZE (AMPERE, VOLTAGE RATING AND TYPE) OF
 DISCONNECT SWITCH AT ELECTRICAL SERVIICE.
 B) THE LOCATION OF THE ELECTRICAL SERVICE.
 C) THE SIZE AND TYPE OF THE SERVICE ENTRANCE CONDUCTORS
 IN THE SERVICE RISER TO THE WEATHERHEAD.
 D) THE SIZE TYPE AND DETAIL OF ALL THE GROUDING
 ELECTROTRODE SYSTEM.
 E) EACH OF THE FEEDERS FROM THE ELECTRICAL SERVICE
 INDICATE 3 CONDUCTORS IN A CONDUIT. THERE IS NO MENTION
 OF A GROUNDING CONDUCTOR. THE ONLY PLACE A GROUNDING
 CONDUCTOR WOULD NOT BE REQUIRED WOULD BE AT THE SERVICE
 ENTRANCE. THE ONLY ALTERNATICE WOULD BE IF THE FEEDER
 CONDUCTORS WERE INSTALLED IN A METLAL CONDUIT WITH THE
 USE OF PROPER GROUNDING LOCKNUTS BONDING BUSINGS ETC...
 F ) THE LOCATION OF THE MAIN HOUSE PANEL
 G) THE OCPD FOR THE SUB PANEL
 H) THE LOCATION OF THE A/C CONDENSING UNITS AND A/C
 AHU'S,THE REQUIRED A/C DISCONNECTS, AND GFI OUTLETS
 WITHIN SITE FOR MECHANICAL EQUIPMENT.
  
 2) REVISE THE RISRE DIAGRAMS, LOAD CALCULATIONS AND
 PANEL SCHEDULES TO CORRECT THE FOLLOWING DEFICIENCIES.
 A) THE OCPD FOR THE SUB PANEL IS NOT INDICATED IN THE
 PANEL SCHEDULE FOR MAIN HOUSE PANEL
 B) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. THE IDENTIFICATION SHALL
 INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. NEC 408.4. "GENERAL
 LIGHTING" OR "CONVENIENCE OUTLETS" IS NOT SUFFICIENT.
 CORRECT BOTH PANEL SCHEDULES.
 C) THE LOAD CALCULATION FOR THE "GUEST HOUSE" INDICATES
 1200 WATTS TO COMPENSATE THE GENERAL LIGHTING LOAD AT 3
 WATTS PER SQUARE FOOT, BUT THEN ALSO ADDS AN ADDITIONAL
 4500WATTS FOR "GENERAL LIGHTING" AND ANOTHER 6000WATTS
 FOR "CONVENIENCE OUTLETS" THIS IS NOT A CODE
 REQUIRMENT, AND IS AN INACCURATE ASSESMENT OF THE
 ACTUAL OR DEMAND LOAD OF THE ELECTRICAL SYSTEM.
 D) EACH OF THE FEEDERS FROM THE ELECTRICAL SERVICE
 INDICATE 3 CONDUCTORS IN A CONDUIT. THERE IS NO MENTION
 OF A GROUNDING CONDUCTOR. THE ONLY PLACE A GROUNDING
 CONDUCTOR WOULD NOT BE REQUIRED WOULD BE AT THE SERVICE
 ENTRANCE. THE ONLY ALTERNATICE WOULD BE IF THE FEEDER
 CONDUCTORS WERE INSTALLED IN A METLAL CONDUIT WITH THE
 USE OF PROPER GROUNDING LOCKNUTS BONDING BUSINGS ETC...
 CLARFY AS NEEDED.
 E) PROVIDE AND INDICATE ON THE FLOOR PLAN AND IN THE
 PANEL SCHEDULES THE USE OF A SEPARATE 20AMP CIRCUIT FOR
 THE BATHROOMS. SUCH OUTLETS SHALL HAVE NO OTHER
 OUTLETS.
  
 3) IDENTIFY THE CIRCUITS ON THE FLOOR PLAN(S) TO THE
 CORRESPONDING CIRCUITS IN BOTH PANEL SCHEDULES.
  
 4) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315. INDICATE THE REQUIRED SMOKE DETECTORS
 THROUGHOUT.
  
 5) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 6) INDICATE OUTLET BOXES USED AS THE SOLE SUPPORT OF A
 CEILING FAN SHALL BE LISTED, SHALL BE MARKED BY THEIR
 MANUFACTURER AS SUITABLE FOR THIS PURPOSE.
  
 7) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11. ADD
 NOTES ACCORDINGLY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  