| 2014-11-18 15:07:01 | BUILDING PLAN REVIEW |
| | PERMIT: 14100651 |
| | ADD: 526 NORTHWOOD |
| | CONT: K & M CONSTRUCTION |
| | TEL: (561)383-2817 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. NOV. 18/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) THE DESCRIPTION OF WORK ON THE PERMIT APPLICATION |
| | AND THE SUBMITTED PLANS APPEARS TO BE DIFFERENT SCOP OF |
| | WORK, IF THE FUTURE ADDITION IS NOT TO BE PART OF THIS |
| | PERMIT PLEASE STRICKE IT FROM THE PLANS, NOT PART OF |
| | THIS PERMIT. THE OTHER ISSUE WITH THE PLAN ARE ALL THE |
| | SHOWN OPENINGS EXISTING OR IS THERE ANY RECONFIGURATION |
| | OF WINDOWS AND OR DOORS INCLUDING NEW COLUMNS AND |
| | LINTELS. |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) THE SUBMITTED PLANS DOES NOT INCLUDE THE WIND DESIGN |
| | CRITERIA FOR THE NEW OPENINGS. |
| | |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 2.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 2.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 2.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) SHEET A-3 VARIOUSELEVATIONS SHOW ORNATE |
| | ARCHITECTURAL FACADE WORK, THERE ARE NO DETAILS HOW THE |
| | FACADE WILL BE MADE OR SECURED TO THE BUILDING. |
| | |
| | 5) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| | OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| | AND DOCUMENTS:FLASHING DETAILS AND WILL THERE BE WOOD |
| | BUCKS FOR WINDOWS AND DOORS? |
| | 1405.12.7 FLASHING. |
| | EXPOSED EDGES OF THIN EXTERIOR STRUCTURAL GLASS VENEER |
| | SHALL BE FLASHED WITH OVERLAPPING CORROSION-RESISTANT |
| | METAL FLASHING AND CAULKED WITH A WATERPROOF COMPOUND |
| | IN A MANNER TO EFFECTIVELY PREVENT THE ENTRANCE OF |
| | MOISTURE BETWEEN THE GLASS VENEER AND THE BACKING. |
| | |
| | 1405.13 EXTERIOR WINDOWS AND DOORS. |
| | WINDOWS AND DOORS INSTALLED IN EXTERIOR WALLS SHALL |
| | CONFORM TO THE TESTING AND PERFORMANCE REQUIREMENTS OF |
| | SECTION 1715.5. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |