| Plan Review Notes For Permit 14100647 |
| Permit Number |
14100647 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-11-01 10:04:44 | 1) A DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1 OF | | | THE 2010 FL. PLUMBING CODE. THE FL. ACCESSIBILITY CODE | | | SEC. 211.2 REQUIRES A MINIMUM OF TWO FOUNTAINS. THE | | | DRINKING FOUNTAINS SHALL COMPLY WITH SECS. 211 & 602 OF | | | THE 2010 FACBC. | | | 2) THE 2" PIPE FOR THE WATER HEATER PAN DRAIN WILL NOT | | | HAVE ANYWAY OF RESEALING THE P-TRAP. COMPLY W/ 2010 FBC | | | SEC.1002.4. | | | 3) THE TWO LAVS IN THE MEN'S RESTROOM REQUIRE VENTS. | | | FPC SEC.901.2, 901.2.1. | | | 4) CLEANOUTS ARE REQD. IN ALL STACKS PER 2010 FPC | | | SEC.708.3.4. | | | 5) THE VIEW OF TWO RESTROOM'S DRAINAGE SYSTEM IS | | | DIFFICULT TO READ DUE TO THE NAMES OF THE RESTROOMS | | | PRINTED OVER THE RISER.SUBMIT A CLEAR, LEGIBLE CODE | | | COMPLIANT RISER DOCUMENT. | | | 6) AS PRESENTLY DESIGNED THERE ARE TWO MANY OF THE SAME | | | TYPE OF FIXTURES ON A WET VENT. COMPLY W/ 2010 FPC | | | SEC.909.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|