| 2015-06-10 16:42:18 | 6/10/2015 |
| | PROJECT: LOFTIN PLACE |
| | PERMIT#: 14030096 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW OF REVISION# 14100630 |
| | ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN |
| | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). |
| | |
| | 1) SHEET E-1.1.1 |
| | RELOCATE NOTE THAT WAS ADDED REGARDING THE SITE AND |
| | LANDSCAPE LIGHTING IN THE VICINITY OF THE POOL. THE |
| | NOTE WAS INADVERTENTLY PLACED ON TOP OF THE PLAN AND IS |
| | DIFFICULT TO SPOT AND READ. RELOCATE THE NOTE FOR |
| | CLARIFICATION TO AN OPEN SPACE ON THE SHEET WHERE IT |
| | WILL BE EASIER TO SPOT AND READ. WPB AMENDMENTS TO FBC |
| | 107. |
| | |
| | 2) E-4.1 |
| | A) THE JUNCTION BOX FOR A ?FUTURE? RADON DETECTOR IS |
| | LOCATED DIRECTLY ABOVE THE BATH TUB. VERIFY THE |
| | LOCATION TO AVOID FUTURE ACCESS, AND INSTALLATION, AND |
| | ISSUES OVER THE TUB WITH THE PROPOSED RADON DETECTORS. |
| | B) CLARIFY THE FIXTURES IN THE CLOTHES CLOSETS MUST |
| | COMPLY WITH THE NEC 410.16 FOR LUMINAIRES IN A CLOTHES |
| | CLOSET. |
| | C) ILLUMINATION IS REQUIRED FOR THE ELECTRICAL AND LOW |
| | VOLTAGE PANELS. NEC 110.26(D) |
| | D) ALL HABITABLE ROOMS REQUIRE A SWITCH LIGHTING |
| | OUTLET. NEC 210.70 |
| | THE BEDROOMS INDICATE A SWITCH CONTROLLED CEILING FAN |
| | BUT NO SWITCH CONTROLLED LIGHT OUTLET. |
| | |
| | 3) E-4.2 |
| | A) THE JUNCTION BOX FOR A ?FUTURE? RADON DETECTOR IS |
| | LOCATED DIRECTLY ABOVE THE BATH TUB. VERIFY THE |
| | LOCATION TO AVOID FUTURE ACCESS, AND INSTALLATION, AND |
| | ISSUES OVER THE TUB WITH THE PROPOSED RADON DETECTORS. |
| | B) CLARIFY THE FIXTURES IN THE CLOTHES CLOSETS MUST |
| | COMPLY WITH THE NEC 410.16 FOR LUMINAIRES IN A CLOTHES |
| | CLOSET. |
| | C) ILLUMINATION IS REQUIRED FOR THE ELECTRICAL AND LOW |
| | VOLTAGE PANELS. NEC 110.26(D) |
| | D) ALL HABITABLE ROOMS REQUIRE A SWITCH LIGHTING |
| | OUTLET. NEC 210.70 |
| | THE BEDROOMS INDICATE A SWITCH CONTROLLED CEILING FAN |
| | BUT NO SWITCH CONTROLLED LIGHT OUTLET. |
| | |
| | 4) E-6.1.1 |
| | SWITCHBOARD ?4?, CIRCUIT 3 FEEDS PANEL L FROM A 350AMP |
| | OCPD AND INDICATES TO REFERENCE THE PANEL SCHEDULE FOR |
| | PANEL ?L? FOR THE FEEDER SIZE. PANEL L DOES NOT |
| | INDICATE THE FEEDER SIZE, NEITHER DOES THE RISER |
| | DIAGRAM. THE RISER DIAGRAM INDICATES TO REFERENCE NOTE |
| | 17 FOR THE FEEDER SIZE. BUT NOTE 17 SAYS TO REFERENCE |
| | THE PANEL SCHEDULE. PROVIDE THE FEEDER SIZE FOR THE |
| | FEEDER FROM SWITCHBOARD ?4? TO PANEL L |
| | |
| | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR SWIMMING POOL, SITE LIGHTING, |
| | GENERATORS, FIRE ALARM, ACCESS CONTROL SYSTEM, |
| | SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, AND, |
| | COMMUNICATION. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |