| | PROJECT: LOFTIN PLACE REVISION |
| | PERMIT#: REVISION TRACKING# 14030096 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW OF REVISION 14100630 |
| | ACTION: DENIED |
| | |
| | SHEET E-1.1.0 |
| | ADD NOTES TO ADDRESS THE AUTOMATIC CONTROL OF INTERIOR |
| | AND EXTERIOR LIGHTING AS REQUIRED THROUGHOUT. FBC |
| | 505.2.2 |
| | THIS NOTE SHOULD ALSO BE ADDED TO THE PANEL SCHEDULES |
| | CONTROLLING LIGHTING IN THESE COMMON AREAS |
| | |
| | SHEET E-1.1.1 |
| | 1) MOVE THE NEW NOTE THAT WAS INCLUDED TO ADDRESS THE |
| | PREVIOUS REVIEW COMMENT REGARDING LIGHTING IN THE |
| | VICINITY OF A SWIMMING POOL. NEC ARTICLE 680.8-10. THIS |
| | NOTE WAS PLACED ON TOP OF THE PLAN RATHER THAN BEING |
| | PLACED IN AN OPEN SPACE FOR CLARITY. |
| | |
| | SHEET E-2.1.1 |
| | 2) MOVE THE NOTE ?ALL CORRIDOR RECEPTACLES SHALL BE |
| | GFCI AND TAMPER RESISTANT? THIS NOTE WAS PLACED ON TOP |
| | OF THE PLAN RATHER THAN BEING PLACED IN AN OPEN SPACE |
| | FOR CLARITY. THE SYMBOL SHOULD BE CHANGED IN ALL |
| | CORRIDORS TO INDICATE THIS PARTICULAR OUTLET TYPE ON |
| | THE FLOOR PLAN. |
| | |
| | SHEET E-4.1 AND E-4.2 |
| | 3) ALL HABITABLE ROOMS REQUIRE A SWITCH LIGHTING |
| | OUTLET. NEC 210.70 |
| | THE BEDROOMS INDICATE A SWITCH CONTROLLED CEILING FAN |
| | BUT NO SWITCH CONTROLLED LIGHT OUTLET. THE GREAT ROOM |
| | INDICATES A SWITCH CONTROLLED RECEPTACLE BUT THE SYMBOL |
| | FOR THE OUTLET IS NOT DESIGNATED AS A SWITCH CONTROLLED |
| | RECEPTACLE. |
| | |
| | 4) THE OUTLETS REQUIRED BY 210.52 (SPACING) DO NOT |
| | INCLUDE THE OUTLETS INDICATED FOR WALL MOUNTED TV?S |
| | WHERE THE RECEPTACLE OUTLET WILL BE INSTALLED ABOVE OR |
| | WHERE THEY ARE CONTROLLED BY A SWITCH SUCH AS IN THE |
| | GREAT ROOM. 210.52 ADDITIONAL RECEPTACLE OUTLET ARE |
| | REQUIRED TO MEET THIS CRITERIA. |
| | |
| | 5) ADDITIONAL OUTLETS ARE REQUIRED AT THE KITCHEN |
| | COUNTERTOP BETWEEN THE STOVE AND THE SINK. 210.52 |
| | |
| | 6) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | PLANS AND ENGINEERING ARE REQUIRED FOR SITE LIGHTING, |
| | GENERATORS. HOOD EXHAUST, FIRE ALARM, ACCESS CONTROL |
| | SYSTEM, SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, |
| | AND, COMMUNICATION. |
| | |
| | SHEET E-4.3 |
| | 7) ADDITIONAL EMERGENCY LIGHTING IS REQUIRED FOR THE |
| | COMMON AREA CORRIDORS, STAIRS, AND LOBBY AREAS. NEC |
| | 700.16, 700.12 |
| | |
| | SHEET E-6.11 |
| | 8) PARKING LOT LIGHTS ARE ALSO REQUIRED TO BE |
| | CONTROLLED SO AS NOT TO BE IN OPERATION WHEN NOT |
| | REQUIRED OR DURING DAYTIME HOURS. THE REQUIREMENTS OF |
| | FBC-ENERGY SECTION 505.2 WILL ALSO APPLY TO THESE |
| | CIRCUITS. |
| | |
| | SHEET E-6.1.2 |
| | 9) A SIMPLE TIME CLOCK IS NOT SUFFICIENT FOR CONTROL OF |
| | THE EXTERIOR LIGHTING TO COMPLY WITH THE FBC-ENERGY |
| | SECTION 505.2. STATES: ?LIGHTING FOR ALL EXTERIOR |
| | APPLICATIONS NOT EXEMPTED IN SECTION 505.1 SHALL HAVE |
| | AUTOMATIC CONTROLS CAPABLE OF TURNING OFF EXTERIOR |
| | LIGHTING WHEN SUFFICIENT DAYLIGHT IS AVAILABLE OR WHEN |
| | THE LIGHTING IS NOT REQUIRED DURING NIGHTTIME HOURS. |
| | LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION |
| | SHALL BE CONTROLLED BY EITHER A COMBINATION OF A |
| | PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME |
| | SWITCH.? |
| | |
| | SHEET E-9.1.1 |
| | 10) REVISE THE LIGHTING FIXTURE SCHEDULE TO INCLUDE THE |
| | FIXTURES STAIRWAY LIGHTING THAT ARE REQUIRED TO HAVE |
| | BATTERY BACKUP. NONE OF THE SYMBOLS IN THE LEGEND |
| | INCLUDE THE FIXTURE SYMBOL THAT HAS BEEN ADDED IN THE |
| | STAIRWAYS THAT REQUIRE BATTERY BACKUP. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |