| Date |
Text |
| 2015-02-28 13:14:22 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. SEE PROVISO ITEM FROM PERMIT ISSUANCE: |
| | |
| | (33). EXITING FROM POOL THROUGH DOOR 138.11 APPEARS TO |
| | ALSO USE 138.9. GATES ARE TO MEET THE SAME REQUIREMENTS |
| | AS DOORS, FBC 1008.2. REVISE TO INCLUDE THE GATE |
| | INFORMATION FOR COMPONENTS SERVING IN THE MEANS OF |
| | EGRESS AROUND THE POOL AREA. PLAN HAS BEEN REDLINED; |
| | PLEASE INCORPORATE INTO ARCHITECT'S DRAWINGS. THIS |
| | SHEET IS NOT REQUIRED TO BE SUBMITTED AT THIS TIME. |
| | |
| | 2ND REVIEW, I APOLOGIZE FOR THE AMBIGUOUS LANGUAGE IN |
| | PREVIOUS REVIEW. PROVISO 33 WAS FROM THE TIME OF PERMIT |
| | ISSUANCE (AND COPIED AND PASTED INTO REVISION REVIEW). |
| | PLAN WAS REDLINED AT THAT TIME WITH THE REQUEST THAT |
| | THE LANGUAGE BE INCORPORATED INTO THE ARCHITECT?S PLAN |
| | BUT NOT REQUIRED TO BE SUBMITTED AT THAT TIME (MEANING |
| | THE TIME OF ISSUANCE OF THE PERMIT). |
| | |
| | THE LANGUAGE WAS NOT INCORPORATED INTO THE PLAN, AS |
| | EVIDENCED BY THE REVISION SUBMITTED WITHOUT THE REVISED |
| | LANGUAGE REGARDING GATES. SO THAT REQUREMENTS ARE CLEAR |
| | TO ALL PARTIES (CONTRACTOR, SUBS, INSPECTORS), PLEASE |
| | INCORPORATE THIS LANGUAGE INTO ARCHITECT'S PLAN AT THIS |
| | TIME. |
| | |
| | 3. A0.1.2 AND OTHER SHEETS (LEVELS), EXIT ACCESS IS |
| | INTERRUPTED BY THE PARKING GARAGE AREA, SEE FBC 1020.1; |
| | LEVEL OF PROTECTION IS TO BE MAINTAINED UNTIL EXIT |
| | DISCHARGE. OCCUPANT ENTERS THE RATED CORRIDOR FROM THE |
| | UNIT, THEN ENTERS THE PARKING GARAGE OR OTHER NON RATED |
| | STORAGE AREA (SEE MARK ON PLAN), THEN ENTERS THE RATED |
| | EXIT STAIR. PLEASE REVISE TO PROVIDE CONTINUOUS |
| | PROTECTION. |
| | 2ND REVIEW, THIS PORTION OF THE PLAN WAS NOT REVISED. |
| | SHEET A0.1.2 HAS BEEN MARKED TO NOTE LOCATION OF NON |
| | CONTINUITY. |
| | |
| | 8. A0.1.5, 8TH LEVEL LIFE SAFETY PLAN, SOME ITEMS FROM |
| | THE ROOF DECK BELOW ARE NOT GREYED OUT. FOR INSTANCE, A |
| | DOOR IS SHOWN OPENING INTO WHAT APPEARS TO BE A |
| | CONCRETE EYEBROW TO WHAT APPEARS TO BE OPEN SPACE, ROOF |
| | DECK BELOW (AT STAIR 3). THIS DOOR IS NOT SHOWN ON |
| | A2.1.8. PLEASE CORRELATE, GREY OUT ITEMS NOT ACTUALLY A |
| | PART OF THE 8TH LEVEL, OR PROVIDE AREA/ROOM DESIGNATION |
| | FOR CLARITY, FBC 107. |
| | 2ND REVIEW, PURPOSE OF THE DOOR IS NOT CLEAR. IT |
| | APPEARS TO OPEN ONTO A DROP TO THE LEVEL BELOW. ALSO |
| | THERE IS ANOTHER AREA WHICH IS NOT CLEAR AS TO WHAT THE |
| | RECTANGLES DEPICT. THESE TWO AREAS HAVE BEEN MARKED |
| | (CLOUDED) ON THE PLAN. |
| | |
| | NEW COMMENTS: |
| | |
| | REV2 1: THIS IS A REMINDER THAT TEST REPORTS FOR |
| | FLOORING UNDERLAYMENT WILL BE REQUIRED PRIOR TO |
| | INSTALLATION. PLEASE BE ADVISED THAT, AT THIS TIME, NO |
| | MANUFACTURER HAS PROVIDED ALL THREE TESTS (FLAME SPREAD |
| | PER FBC 603.1/803.1.1, IIC PER FBC 1207.3, STC PER FBC |
| | 1207.2) FOR TILE ON A 6" SLAB WITHOUT A DROPPED |
| | CEILING. IF YOU DO NOT INTEND TO FIELD TEST FOR SOUND |
| | (SO A STC/IIC OF 45 IS REQUIRED RATHER THAN 50) YOU ARE |
| | ENCOURAGED TO ADDRESS THIS ISSUE TIMELY. PLEASE FEEL |
| | FREE TO CONTACT ME TO DISCUSS WHEN YOU ARE READY TO |
| | MAKE THE FLOORING UNDERLAYMENT SELECTION. |
| | |
| | REV2 2: LOUVERS ARE SHOWN ON SHEET A2.1.2 AND POSSIBLY |
| | OTHER LOCATIONS, GLASS BLOCK SHOWN ON LEGEND ON A SHEET |
| | ELEVATIONS (FOR EXAMPLE, A3.1.2). PRODUCT APPROVALS FOR |
| | ALL COMPONENTS, CLADDING, LOUVERS ARE TO BE SUBMITTED |
| | (AS A SUBMITTAL, NO FEE) FOR REVIEW PRIOR TO |
| | INSTALLATION. REVIEW BY DESIGNER OF RECORD REQUIRED |
| | PRIOR TO SUBMITTAL. IF SUBMITTED IN PAPER FORM, THREE |
| | SETS REQUIRED. PLEASE NOTE THAT DIGITAL ONLY WILL BE |
| | REQUIRED AT SOME POINT IN THE NEAR FUTURE. |
| | |
| | REV2 3: A2.1.6, A PORTION OF TWO APARTMENTS AND WHAT |
| | APPEARS TO POSSIBLY BE STAIR #2 ARE SHOWN OUTSIDE OF |
| | THE BUILDING ENVELOPE (NW CORNER OF BUILDING). THIS HAS |
| | BEEN MARKED (CLOUDED) ON THE SHEET. PLEASE REMOVE OR |
| | CLARIFY. |
| | |
| | REV2 4: SHEET S0.3 GENERAL NOTE M11 REFERS TO NOA |
| | 14-0903.02 (CAST CRETE LINTELS). WHEN RESUBMITTING, |
| | PLEASE UPLOAD THIS NOA FOR THE PERMIT RECORD. |
| | |
| | REV2 5: SHEET M2.1.3, CORRIDOR TO STORAGE (SE PORTION |
| | OF BUILDING), PENETRATIONS THROUGH RATED WALLS REQUIRE |
| | A FIRE DAMPER, FBC 709.9, 716. 4TH FLOOR ALSO MISSING |
| | FD IN SAME LOCATION. CHECK ALL AND REVISE ACCORDINGLY. |
| | |
| | |
| | |
| | |