| | WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 1) DWG. P-5.1 - THE WATER RISER FOR UNIT # B1 APPEARS |
| | TO HAVE THE PIPE SIZES REVERSED AND THE HOT AND COLD |
| | WATER LINES ARE REVERSED AT SOME OF THE FIXTURES. MOST |
| | OF THE FIXTURES ARE BEING FED FROM A 1/2 " COLD WATER |
| | LINE. |
| | 2) DWG. P-5.4C - RISER #117 - THE VENT STACK IS SHOWN |
| | AS 3" AND ON SHT. P-5.3 IT IS SHOWN AS 4". CLARIFY. |
| | 3) SHT.P-5.4C - RISER #113 IS LABELED AS RISER #13 - |
| | CORRECT |
| | 4) DWG.P-5.2 - PLEASE EXPLAIN HOW YOU ARRIVED AT THE |
| | FIXTURE UNIT LOAD FOR THE WATER PIPING. |
| | 5) WG. P-5.5 - STORM COLLECTION RISER #1 - A 3" ROOF |
| | DRAIN WITH A COLLECTION AREA OF 1520 SQ. FT.IS |
| | DISCHARGING INTO A HORIZONTAL LINE THAT IS 4 " IN |
| | DIAMETER. THE MAXIMUM SQUARE FOOTAGE PERMITTED ON A 4" |
| | LINE AT MIN. 1/8" SLOPE IS 1504 SQ. FT. THIS LINE HAS |
| | TO BE INCREASED TO 5 " OR THE SLOPE OF THE PIPE SHALL |
| | BE INCREASED TO 1/4 " SLOPE PER FT. |
| | 6) PROVIDE A LEGEND FOR THE HOT AND COLD WATER LINES ( |
| | THE WATER RISERS SHOW THE LINES IDENTIFIED WITH ONE AND |
| | TWO DASHES. JUST IDENTIFY WHICH ONE IS FOR HOT AND |
| | WHICH ONE IS FOR COLD). |
| | 7) SHT. P-5.3 - THE BOTTOM HALF OF THE PAGE - THE |
| | GROUPS OF RISER NUMBERS ARE SPACED SO CLOSE TO EACH |
| | OTHER THAT IT IS DIFFICULT TO FIGURE OUT WHICH RISER |
| | NUMBERS APPLY TO THE SPECIFIC RISERS. |
| | 8) DWG. P-5.3 - SHOWS RISER # 117 FOR TWO DIFFERENT |
| | RISERS - CLARIFY. |
| | 9) DWG.P-6.2 - A WATER HAMMER ARRESTOR SHALL BE |
| | INSTALLED ON THE TRASH CHUTE WASHDOWN PER 2010 FPC |
| | SEC.604.9. |
| | 10) DWG. P-6.2 - THE EJECTOR SHALL BE PROVIDED WITH A |
| | FULL FLOW VALVE ( SHUTOFF VALVE) AND CHECK VALVE |
| | LOCATED IN THE DISCHARGE PIPING BETWEEN THE PUMP OR |
| | EJECTOR AND THE GRAVITY DRAINAGE SYSTEM. 2010 FPC |
| | SEC.712.2. |
| | 11) IF THE ELEVATOR IS A HYDRAULIC ELEVATOR THE |
| | EFFLUENT FROM THE SUMP PIT SHALL DISCHARGE INTO AN OIL |
| | SEPARATOR. INDICATE ON THE DRAWING IF THE ELEVATOR IS |
| | CBLE DRIVEN OR HYDRAULIC. |
| | 12) DWG. P-6.2 - INDICATE ON THE PLAN WHETHER THE FLOOR |
| | DRAIN RECEIVING THE WASTE FROM THE ELEVATOR PIT IS |
| | DISCHARGING TO THE STORM OR SANITARY. |
| | 13) DWG. P-5.4B - INDICATE THE SLOPE OF THE 8" SANITARY |
| | LINE ON THE DRAWING. COMPLY W/2010 FPC TABLE 710.1 (1) |
| | FOR THE SLOPE OF PIPE AND THE MAXIMUM NUMBER OF FIXTURE |
| | UNITS THAT THE PIPE CAN CARRY. |
| | 14) ANY WASHING MACHINE BOXES LOCATED IN FIRE RATED |
| | WALLS SHALL EITHER BE FIRE RATED OR INSTALLED TO |
| | MAINTAIN THE FIRE RATING OF THE WALL. 2010 FBC SEC.713. |
| | 15) DWG. P-6.2 - THE P & T LINES AND PAN DRAINS SHALL |
| | NOT USE THE SAME RISER PER THE 2010 FPC SEC.504.6 (4). |
| | 16) DWG.P-6.2 - THE PAN DRAIN SHALL BE DRAINED BY AN |
| | INDIRECT WASTE PIPE PER THE 2010 FPC SEC. 504.7.1. |
| | 17) DWG. P-5.6A - SHOWS THE RELIEF LINES AS A DIRECT |
| | CONNECTION TO THE RISER AND THE WATER HEATER DETAIL ON |
| | DWG. P-6.2 SHOWS RELIEF LINES DISCHARGING TO AN AIR GAP |
| | FITTING . CLARIFY. |
| | 18) COMBUSTIBLE MATERIALS ARE NOT PERMITTED IN RETURN |
| | AIR PLENUMS PER THE 2010 FPC SEC.307.6 FL. MECH CODE. |
| | SEC.602.2.1. |
| | |