| 2014-12-12 09:33:05 | 12/11/2014 |
| | PROJECT: LOFTIN PLACE REVISION |
| | PERMIT#: 14030096 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW OF REVISION 14100630 |
| | ACTION: DENIED |
| | |
| | SHEET E-1.1.1 |
| | 1) VERIFY THE LOCATION, AND ELEVATION OF POWER AND |
| | LIGHTING INCLUDING THEIR ASSOCIATED CONDUITS AND WIRING |
| | IN THE VICINITY OF THE SWIMMING POOL. NEC680.8.680.10, |
| | 680.22, 680.24 |
| | |
| | SHEET E-2.1.2 |
| | 1) EMERGENCY LIGHTING SHALL BE FED BY LIGHTING CIRCUIT |
| | OF SAME LOCAL AREA. NEC 700.12 (F) (4) |
| | |
| | E.2.1.7 |
| | 2) LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED |
| | IN SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE |
| | OF TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT |
| | DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING IS NOT |
| | REQUIRED DURING NIGHTTIME HOURS. LIGHTING NOT |
| | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE |
| | CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND |
| | A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. FBC |
| | 505.2.4 EXTERIOR LIGHTING CONTROLS. |
| | |
| | 3) PROVIDE WIND LOAD CALCULATIONS FOR ALL LIGHT POLES |
| | INCLUDING LUMINAIRE IN COMPLIANCE WITH THE FBC 1609 |
| | |
| | SHEET E-4.1 |
| | 4) STUDIO ONE UNIT REQUIRES AN OUTLET AT THE KITCHEN |
| | ISLAND. NEC 210.52 |
| | |
| | SHEET 4.1A |
| | 5) PANEL A1 INDICATES CIRCUIT #1,3 FOR THE A/C IS A |
| | 2POLE 35 WITH #12. REVISE THE PANEL SCHEDULE TO |
| | INDICATE A CIRCUIT CONDUCTOR ADAQUATE FOR THE 35AMP |
| | OCPD. NEC 310.16 |
| | |
| | E-4.3 |
| | 6) THE CORRIDORS AND COMMON AREAS REQUIRE EMERGENCY |
| | LIGHTING. LIGHTING SYSTEMS SHALL BE DESIGNED AND |
| | INSTALLED SO THAT THE FAILURE OF ANY INDIVIDUAL |
| | LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF A LAMP, |
| | CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT REQUIRES |
| | EMERGENCY ILLUMINATION. NEC 700.16 |
| | |
| | 7) IDENTIFY ALL LIGHTING CIRCUITS ON THE FLOOR PLAN. |
| | FBC 107.3.2 |
| | |
| | 8) EMERGENCY LIGHTING SHALL BE FED BY LIGHTING CIRCUIT |
| | OF SAME LOCAL AREA. NEC 700.12 (F) (4) |
| | |
| | E-4.4 |
| | 9) PROVIDE EMERGENCY LIGHTING FOR STAIRWELLS. EMERGENCY |
| | LIGHTING SYSTEMS SHALL BE DESIGNED AND INSTALLED SO |
| | THAT THE FAILURE OF ANY INDIVIDUAL LIGHTING ELEMENT, |
| | SUCH AS THE BURNING OUT OF A LAMP, CANNOT LEAVE IN |
| | TOTAL DARKNESS ANY SPACE THAT REQUIRES EMERGENCY |
| | ILLUMINATION. NEC 700.16 |
| | |
| | E-5.1.1 |
| | 10) CLARIFY THE CIRCUIT FEEDING THE FIRE PUMP. THE |
| | RISER ON 7.1.1 INDICATES THE FIRE PUMP SERVICE FROM THE |
| | UTILITY TO THE FIRE PUMP CONTROLLER AND THE FLOOR PLAN |
| | ON SHEET 5.1.1 INDICATES THE FIRE PUMP BEING FED FROM |
| | SWITCHBOARD 4 CIRCUIT #10 AND THE PANEL SCHEDULE FOR |
| | SWITCH BOARD 4 CIRCUIT #10 INDICATES A SPACE. REVISE |
| | THE FLOOR PLAN ON SHEET 5.1.1 TO INDICATE THE ACTUAL |
| | FEEDER. |
| | |
| | E-6.1.1 |
| | 11) REVISE PANEL SCHEDULES AND LOAD CALCULATIONS IN |
| | SWITCH BOARD 2 AND 3. THE TOTAL CALCULATED LOADS |
| | REPRESENTED IN THE CHART LABELED TOTAL UNIT CONNECTED |
| | LOAD STATES THE TOTAL CONNECTED LOAD IN VA PER METER |
| | CENTER. THE PANEL SCHEDULE FOR SWITCH BOARD ?3? |
| | INDICATES THE LOADS TO BE SLIGHTLY DIFFERENT THAN WHAT |
| | IS REPRESENTED IN THE CHART ON E7.1.1 PARTICULARLY THE |
| | LOAD FOR METER CENTER 8. THE PANEL SCHEDULE ON E6.1.1 |
| | INDICATES MC 8 WITH A TCL OF 847.7KVA BUT THE LOAD |
| | INDICATED IN THE CHART ON E7.1.1 IS INDICATED TO BE |
| | 1,078,144VA OR 1,078KVA. REVISE LOADS IN PANEL |
| | SCHEDULES AND LOAD CALCULATIONS TO BE ACCURATE AND TO |
| | MATCH FROM PAGE TO PAGE |
| | |
| | E-7.1.1. AND E-7.1.2 |
| | 12) NEC240.4(C) WHERE THE OVERCURRENT DEVICE IS RATED |
| | OVER 800 AMPERES, THE AMPACITY OF THE CONDUCTORS IT |
| | PROTECTS SHALL BE EQUAL TO OR GREATER THAN THE RATING |
| | OF THE OVERCURRENT DEVICE DEFINED IN NEC 240.6. 3 SETS |
| | OF 500MCM CU IS NOT ADEQUATE FOR A 1200AMP OCPD |
| | 13) VERIFY SAME FOR ALL SERVICE ENTRANCE AND FEEDERS |
| | |
| | 14) NEC240.4(C) DEVICES RATED OVER 800 AMPERES. WHERE |
| | THE OVERCURRENT DEVICE IS RATED OVER 800 AMPERES, THE |
| | AMPACITY OF THE CONDUCTORS IT PROTECTS SHALL BE EQUAL |
| | TO OR GREATER THAN THE RATING OF THE OVERCURRENT DEVICE |
| | DEFINED IN NEC 240.6 |
| | 3 SETS OF 500MCM CU IS NOT ADEQUATE FOR A 1200AMP OCPD |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |