Plan Review Notes
Plan Review Notes For Permit 14100616
Permit Number 14100616
Review Stop P
Sequence Number 2
Notes
Date Text
2014-11-22 09:14:531) SHOW THE SIZES FOR THE WATER DISTIBUTION LINES TO
 THE FIXTURES FOR BATHROOMS NUMBER 158 & 159. 2ND
 REQUEST.
 2) THE GAS LINE CARRYING 2071 CFH IS UNDERSIZED AT 1
 1/4". THE MAXIMUM BTU LOAD FOR 1 1/4' PIPE @2 PSI & 300
 FT. RUN IS 1,940,000. THE SIZE SHALL BE 1 1/2".
 3) THE PIPE SIZES ON THE WATER RISER ARE SO SMALL THEY
 ARE ILLEGIBLE. SIZE THE LINES SO THE DIMENSION IS CLEAR
 AND LEGIBLE. WPB AMEND. TO 2010 FPC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW