Plan Review Notes
Plan Review Notes For Permit 14100616
Permit Number 14100616
Review Stop P
Sequence Number 1
Notes
Date Text
2014-11-01 06:50:201) IT APPEARS THAT THE HOT WATER SYSTEM REQUIRES A
 METHOD OF HOT WATER SUPPLY MAINTENANCE PER SEC. 607.2
 OF THE 2010
 FPC.607.2 HOT WATER SUPPLY TEMPERATURE MAINTENANCE.
 WHERE THE DEVELOPED LENGTH OF HOT WATER PIPING FROM THE
 SOURCE OF HOT WATER SUPPLY TO THE FARTHEST FIXTURE
 EXCEEDS 100 FEET (30 480 MM), THE HOT WATER SUPPLY
 SYSTEM SHALL BE PROVIDED WITH A METHOD OF MAINTAINING
 THE TEMPERATURE IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, ENERGY CONSERVATION.
 2) THERE ARE A LOT OF SECTIONS ON THE WATER RISER THAT
 ARE NOT SIZED. CHECK ALL THE SECTIONS AND SIZE THE
 LINES THAT REQUIRE THE SIZING. SEE THE WATER
 DISTRIBUTION PIPING FOR THE RESTROOMS ALSO. WPB AMEND.
 TO 2010 FPC SEC.107.2.1.
 3) SUBMIT MANUF. SPEC SHEETS AND INSTALLATION MANUAL
 FOR THE POINT OF USE WATER HEATERS.WPB AMEND. TO 2010
 FPC SEC.107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  