| 2014-12-22 11:46:21 | 12/22/2014 |
| | PROJECT: MURRAY ROAD HOUSE |
| | PERMIT#: 14100615 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION |
| | |
| | 1) FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| | TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| | ONE RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT |
| | GRADE LEVEL AND LOCATED NOT MORE THAN 2.0 M (61.2 FT) |
| | ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF |
| | THE DWELLING. NEC 210.52(E)(3) |
| | |
| | 2) ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, |
| | AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. NEC |
| | 210.63 SEE 210.8(A)(3) |
| | |
| | 3) ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| | RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1) |
| | THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION FOR PERSONNEL. NEC 210.8(A)(6) WITHIN 6' OF |
| | THE SINK. |
| | |
| | 4) VERIFY SUFFICIENT ACCESS AND WORKING SPACE SHALL BE |
| | PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT |
| | TO PERMIT READY AND SAFE OPERATION AND MAINTENANCE OF |
| | SUCH EQUIPMENT. NEC 110.26 |
| | |
| | 5) VERIFY RECEPTACLE SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 1.8 |
| | M (6 FT) FROM A RECEPTACLE OUTLET. NEC 210.52 |
| | |
| | 6) AS BUILT REQUIRED IF PROJECT IS DIFFERENT THAN |
| | PLANS. A CIRCUIT #13 IN THE PANEL SCHEDULE IS |
| | IDENTIFIED AS NEW LIGHTING AT BEDROOM AND BATH. |
| | INDICATE ANY NEW WORK ON THE PLANS. FBC-WPB AMENDMENTS |
| | 107.3.2 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |