2014-12-23 13:42:0412/23/14 ZONING FAILED
  
 1. CARPORT DOES NOT MEET SETBACKS, POSTS ARE ONLY 2.3
 FROM THE SIDE YARD.
2014-12-22 08:21:15PLAN REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 BUILDING
  
 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.
  
 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 EXTERIOR DOORS ( FL-15180.40 ), THE SINGLE HUNG WINDOWS
 ( NOA NO. 12-0213.05 ) AND THE ALUMINUM TUBE MULLIONS (
 NOA NO. 12-0221.09 ) HAVE NOT BEEN REVIEWED AND
 APPROVED IN WRITING BY THE ENGINEER AS REQUIRED BY FBC
 107.3.4.
  
 3) THE INSTALLATION DRAWINGS FOR THE WINDOWS AND
 MULLIONS WERE NOT SHRUNK TO FIT ON THE 8.5" X 11" SIZE
 PAPER AND ARE MISSING INFORMATION. SUBMIT PRODUCT
 APPROVALS WITH COMPLETE DRAWINGS. DCA RULE 9N-3 AND FBC
 107.2.1
  
 4) THERE ARE TWO DIFFERENT EXPOSURE CATEGORIES
 SPECIFIED ON THE PLANS. THE SHEET S-1 HAS "D" AND SHEET
 S-3 HAS "C". THERE CAN BE ONLY ONE EXPOSURE CATEGORY
 AND "C" IS THE CORRECT ONE. FBCR 301.2.1.1
  
 5) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 ALUMINUM ROOF PANELS THAT HAVE BEEN REVIEWED AND
 APPROVED BY IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. DCA RULE 9N-3 AND FBC 107.3.4
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  