| 2014-11-21 14:28:40 | PLAN REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | BUILDING |
| | |
| | 1) THE ENGINEER'S SEAL THAT APPEARS ON THE PLANS IS NO |
| | LONGER ACCEPTABLE. THE SEAL WAS CHANGED ON JANURARY 1, |
| | 2006 REQUIRING THE WORD "LICENSE" TO BE USED INSTEAD OF |
| | THE WORD "CERTIFICATE". PLEASE SUBMIT PLANS THAT HAVE A |
| | SEAL THAT IS ACCEPTED BY THE BOARD OF ENGINEERS. FS 471 |
| | |
| | 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. |
| | A) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | SINGLE HUNG WINDOWS ( NOA NO. 12-0213.05 ) AND THE |
| | ALUMINUM TUBE MULLIONS ( NOA NO. 12-0221.09 ) HAVE NOT |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE ENGINEER. |
| | B) THE INSTALLATION DRAWINGS WERE NOT SHRUNK TO FIT ON |
| | THE 8.5" X 11" SIZE PAPER AND ARE MISSING INFORMATION. |
| | SUBMIT PRODUCT APPROVALS WITH COMPLETE DRAWINGS. |
| | C) NO PRODUCT APPROVALS WERE SUBMITTED FOR THE EXTERIOR |
| | DOORS. SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE |
| | EXTERIOR DOORS THAT HAVE BEEN REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 3) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. SHOW SMOKE |
| | ALARMS ON THE PLANS. |
| | |
| | 4) SPECIFY THE WIND DESIGN DATA INCLUDING THE EXPOSURE |
| | CATEGORY ON THE PLANS. FBCR 301.2.1.1 |
| | |
| | 5) SPECIFY THE REQUIRED COMPONENT & CLADDING PRESSURES |
| | FOR THE WINDOW AND DOORS ON THE PLANS. FBCR 301.2.1 THE |
| | C & C PRESSURES THAT WERE SPECIFIED ON THE PLANS ( +80 |
| | , -115 PSF ) AND (+50 , -50 PSF )ARE INCORRECT. |
| | |
| | 6) PROVIDE COMPLETE STRUCTURAL DRAWINGS AND DETAILS FOR |
| | THE NEW CARPORT TO SHOW THAT IT COMPLIES WITH FBC-R |
| | 301.1. BUILDINGS AND STRUCTURES, AND ALL PARTS THEREOF, |
| | SHALL BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, |
| | INCLUDING DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOD |
| | LOADS, AND WIND LOADS AS PRESCRIBED BY THIS CODE. THE |
| | CONSTRUCTION OF BUILDINGS AND STRUCTURES IN ACCORDANCE |
| | WITH THE PROVISIONS OF THIS CODE SHALL RESULT IN A |
| | SYSTEM THAT PROVIDES A COMPLETE LOAD PATH THAT MEETS |
| | ALL REQUIREMENTS FOR THE TRANSFER OF ALL LOADS FROM |
| | THEIR POINT OF ORIGIN THROUGH THE LOAD-RESISTING |
| | ELEMENTS TO THE FOUNDATION. SPECIFY THE FOUNDATION AND |
| | SLAB SIZE AND RE-INFORCEMENT, THE COLUMN, BEAM AND |
| | RAFTER SIZES AND TYPE OF WOOD. SPECIFY THE RAFTER |
| | SPACING AND THE ROOF SHEATHING THAT IS REQUIRED. |
| | SPECIFY ALL OF THE ANCHORS, STRAPS, HANGERS AND |
| | FASTENERS THAT WILL BE REQUIRED. FBC 107.2.1 AND |
| | 107.2.1.3 IF THE INFORMATION FOR THE ALUMINUM CARPORT |
| | IS NOT PROVIDED WITH THIS SUBMITTAL, THEN A SEPERATE |
| | PERMIT, APPLICATION AND REVIEW WILL BE REQUIRED. NOTE |
| | ON PLANS THAT THE CARPORT AND FRONT PORCH AWNING ARE |
| | UNDER SEPARATE PERMITS OR SUBMIT ALL REQUESTED |
| | INFORMATION. |
| | |
| | 7) SHEET C-1, WHICH IS LISTED IN THE DRAWING INDEX ON |
| | SP-1, IS MISSING FROM THE PLANS. SUBMIT THE MISSING |
| | DRAWING OR REVISE THE DRAWING INDEX. |
| | |
| | 8) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE |
| | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER |
| | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN |
| | ADDRESSED. |
| | |
| | RESUBMITTAL PROCEDURE |
| | YOU ARE REQUIRED TO FILL OUT A RESUBMITTAL FORM TO BE |
| | SUBMITTED WITH THE CORRECTED PLANS. |
| | THE PERMIT CLERK WILL RETRIEVE THE DENIED APPLICATION, |
| | PLANS AND OTHER DOCUMENTS FOR YOU. |
| | YOU ARE REQUIRED TO REMOVE THE OLD PLAN SHEETS THAT |
| | HAVE BEEN CORRECTED AND REPLACE THEM WITH THE NEW ONES. |
| | THE CLERK WILL PROVIDE YOU WITH A STAPLE REMOVER AND A |
| | STAPLER. ONE SET OF THE OLD PLAN SHEETS THAT HAVE BEEN |
| | REMOVED SHALL BE MARKED AS VOIDED AND RESUBMITTED ALONG |
| | WITH THE TWO (OR MORE) SETS THAT CONTAIN THE CORRECTED |
| | SHEETS. IF THERE ARE ANY SHEETS THAT HAVE BEEN STAMPED |
| | FOR COUNTY IMPACT FEES, HOA APPROVAL STAMPS OR OTHERS, |
| | RESUBMIT THOSE SHEETS. |
| | IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO |
| | (OR MORE) SETS OF THE NEW PLANS SHALL BE SUBMITTED. |
| | |
| | |
| | |
| | |