| | PROJECT: MURRAY RD. HOUSE |
| | PERMIT#: 14100615 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) COUNTERTOP OUTLETS IN THE KITCHEN SHALL BE INSTALLED |
| | IN ACCORDANCE WITH THE PROVISIONS OF NEC 210.52(C) AT |
| | LEAST ONE ADDITIONAL OUTLET(S) IS REQUIRED. |
| | |
| | 2) ELECTRICAL FLOOR PLAN DOES'NT MATCH ARCHITECTURAL |
| | FLOOR PLAN. THE LAUNDRY RM IS LOCATED IN A DIFFERENT |
| | LOCATION ON EACH. |
| | |
| | 3) IDENTIFY OUTLETS ON THE FLOOR PLAN WITH CORESPONDING |
| | CIRCUIT NUMBERS FROM THE PANEL SCHEDULE. WPB AMENDMENTS |
| | TO THE FBC 107.3.2 |
| | |
| | 4) PROVIDE A PANEL SCHEDULE INDICATING THE CIRCUIT |
| | NUMBERS, ROOM/DEVICE DESIGNATIONS, AMP AND VOLTAGE |
| | RATINGS.WPB AMENDMENTS TO THE FBC 107.3.2 |
| | |
| | 5) INDICATE THE LOCATIONS AND CIRCUITING OF SMOKE/CO |
| | DETECTORS. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | FBC-RESIDENTIAL 314 AND 315 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |