 PROJECT: MURRAY RD. HOUSE
 PERMIT#: 14100615
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) COUNTERTOP OUTLETS IN THE KITCHEN SHALL BE INSTALLED
 IN ACCORDANCE WITH THE PROVISIONS OF NEC 210.52(C) AT
 LEAST ONE ADDITIONAL OUTLET(S) IS REQUIRED.
  
 2) ELECTRICAL FLOOR PLAN DOES'NT MATCH ARCHITECTURAL
 FLOOR PLAN. THE LAUNDRY RM IS LOCATED IN A DIFFERENT
 LOCATION ON EACH.
  
 3) IDENTIFY OUTLETS ON THE FLOOR PLAN WITH CORESPONDING
 CIRCUIT NUMBERS FROM THE PANEL SCHEDULE. WPB AMENDMENTS
 TO THE FBC 107.3.2
  
 4) PROVIDE A PANEL SCHEDULE INDICATING THE CIRCUIT
 NUMBERS, ROOM/DEVICE DESIGNATIONS, AMP AND VOLTAGE
 RATINGS.WPB AMENDMENTS TO THE FBC 107.3.2
  
 5) INDICATE THE LOCATIONS AND CIRCUITING OF SMOKE/CO
 DETECTORS. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 FBC-RESIDENTIAL 314 AND 315
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  