2014-11-06 16:08:07PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 THE PLANS THAT WERE SUBMITTED APPEAR TO BE UNFINISHED
 AND INCOMPLETE.
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 BUILDING
  
 1) THE ENGINEER'S SEAL THAT APPEARS ON THE PLANS IS NO
 LONGER ACCEPTABLE. THE SEAL WAS CHANGED ON JANURARY 1,
 2006 REQUIRING THE WORD "LICENSE" TO BE USED INSTEAD OF
 THE WORD "CERTIFICATE". PLEASE SUBMIT PLANS THAT HAVE A
 SEAL THAT IS ACCEPTED BY THE BOARD OF ENGINEERS. FS 471
  
 2) SPECIFY THE DISTANCE FROM THE NEW CARPORT ADDITION
 TO THE PROPERTY LINE ON THE PLANS. FBCR 302 AND TABLE
 R302.1 REQUIRES A MINIMUM FIRE SEPARATION DISTANCE OF 3
 FEET FOR WALLS AND ROOF OVERHANG PROJECTIONS WITHOUT
 FIRE-RESISTANCE RATINGS.
  
 3) SPECIFY THE WINDOW TYPES AND DIMENSIONS ON THE
 PLANS.
  
 4) SPECIFY THE DOOR TYPES AND DIMENSIONS ON THE PLANS.
  
 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING,
 WINDOW, AND DOOR STATE OF FLORIDA OR MIAMI-DADE NOAS.
  
 6) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 7) R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
  
 8) R301.2.1.2 PROTECTION OF OPENINGS.
 WINDOWS IN BUILDINGS LOCATED IN WINDBORNE DEBRIS
 REGIONS SHALL HAVE GLAZED OPENINGS PROTECTED FROM
 WINDBORNE DEBRIS. GLAZED OPENING PROTECTION FOR
 WINDBORNE DEBRIS SHALL MEET THE REQUIREMENTS OF THE
 LARGE MISSILE TEST OF ASTM E 1996, ASTM E 1886, SSTD 12
 OR TAS 201, 202 AND 203 OR AAMA 506 REFERENCED THEREIN.
 IF GLAZING IN THE WIDOWS AND DOORS IS NOT RATED FOR
 LARGE MISSILE IMPACT, THEN SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE IMPACT PROTECTION DEVICES, AN
 INSTALLATION SCHEDULE AND A KEY PLAN.
  
 9) SPECIFY THE WIND DESIGN DATA INCLUDING THE EXPOSURE
 CATEGORY ON THE PLANS. FBCR 301.2.1.1
  
 10) SPECIFY THE COMPONENT & CLADDING PRESSURES FOR THE
 WINDOW AND DOORS ON THE PLANS. FBCR 301.2.1
  
 11) PROVIDE COMPLETE STRUCTURAL DRAWINGS AND DETAILS
 FOR THE NEW CARPORT TO SHOW THAT IT COMPLIES WITH FBC-R
 301.1. BUILDINGS AND STRUCTURES, AND ALL PARTS THEREOF,
 SHALL BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS,
 INCLUDING DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOD
 LOADS, AND WIND LOADS AS PRESCRIBED BY THIS CODE. THE
 CONSTRUCTION OF BUILDINGS AND STRUCTURES IN ACCORDANCE
 WITH THE PROVISIONS OF THIS CODE SHALL RESULT IN A
 SYSTEM THAT PROVIDES A COMPLETE LOAD PATH THAT MEETS
 ALL REQUIREMENTS FOR THE TRANSFER OF ALL LOADS FROM
 THEIR POINT OF ORIGIN THROUGH THE LOAD-RESISTING
 ELEMENTS TO THE FOUNDATION. SPECIFY THE FOUNDATION AND
 SLAB SIZE AND RE-INFORCEMENT, THE COLUMN, BEAM AND
 RAFTER SIZES AND TYPE OF WOOD. SPECIFY THE RAFTER
 SPACING AND THE ROOF SHEATHING THAT IS REQUIRED.
 SPECIFY ALL OF THE ANCHORS, STRAPS, HANGERS AND
 FASTENERS THAT WILL BE REQUIRED. FBC 107.2.1 AND
 107.2.1.3
  
 12) FBC-R803.2.3.1 SHEATHING FASTENINGS.
 WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED TO
 ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON
 CENTER AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE
 FRAMING. RING-SHANK NAILS SHALL HAVE THE FOLLOWING
 MINIMUM DIMENSIONS:
 1. 0.113 INCH NOMINAL SHANK DIAMETER.
 2. RING DIAMETER OF 0.012 OVER SHANK DIAMETER.
 3. 16 TO 20 RINGS PER INCH.
 4. 0.280 INCH FULL ROUND HEAD DIAMETER.
 5. 2 INCH NAIL LENGTH.
 WHERE ROOF FRAMING WITH A SPECIFIC GRAVITY, 0.42 < G <
 0.49 IS USED, SPACING OF RING-SHANK FASTENERS SHALL BE
 4 INCHES ON CENTER IN NAILING ZONE 3 IN ACCORDANCE WITH
 FIGURE R803.2.3.1 WHERE VASD AS DETERMINED IN
 ACCORDANCE WITH SECTION R301.2.1.3 IS 130 MPH OR
 GREATER.
  
 13) SHEET C-1, WHICH IS LISTED IN THE DRAWING INDEX ON
 SP-1, IS MISSING FROM THE PLANS.
  
 14) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
 RESUBMITTAL PROCEDURE
 YOU ARE REQUIRED TO FILL OUT A RESUBMITTAL FORM TO BE
 SUBMITTED WITH THE CORRECTED PLANS.
 THE PERMIT CLERK WILL RETRIEVE THE DENIED APPLICATION,
 PLANS AND OTHER DOCUMENTS FOR YOU.
 YOU ARE REQUIRED TO REMOVE THE OLD PLAN SHEETS THAT
 HAVE BEEN CORRECTED AND REPLACE THEM WITH THE NEW ONES.
 THE CLERK WILL PROVIDE YOU WITH A STAPLE REMOVER AND A
 STAPLER. ONE SET OF THE OLD PLAN SHEETS THAT HAVE BEEN
 REMOVED SHALL BE MARKED AS VOIDED AND RESUBMITTED ALONG
 WITH THE TWO (OR MORE) SETS THAT CONTAIN THE CORRECTED
 SHEETS. IF THERE ARE ANY SHEETS THAT HAVE BEEN STAMPED
 FOR COUNTY IMPACT FEES, HOA APPROVAL STAMPS OR OTHERS,
 RESUBMIT THOSE SHEETS.
 IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO
 (OR MORE) SETS OF THE NEW PLANS SHALL BE SUBMITTED.
  
  
  
  
  
  
  
  