| Plan Review Notes For Permit 14100612 |
| Permit Number |
14100612 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-11-27 07:52:48 | 1) THE SHOWER SHALL BE HANDICAPPED ACCESSIBLE PER THE | | | 2010 FL. ACCESSIBILITY CODE SECS. 213.3.6 & 608 , | | | 309.4. SUBMIT ALL DETAILS. 2ND REQUEST. | | | 2) SHT. P0-1 - SECTION 905.3 2010 FPC - VENT CONNECTION | | | TO DRAINAGE SYSTEM - EVERY DRY VENT CONNECTING TO A | | | HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF | | | THE HORIZONTAL DRAIN PIPE. 2ND REQUEST. | | | 3) SIZE THE VENT FOR THE SHOWER ON THE PLAN.COMPLY | | | W/FPC SEC.916.1 & TABLE 906.1 OF THE 2010 FPC.2ND | | | REQUEST. | | | 4) MEP PLANS SHALL BE SIGNED & SEALED BY THE DESIGN | | | PROFESSIONAL OF RECORD PER THE FL. ADMIN. CODE RULE | | | 61G15-23.001 & 23.002. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|