| Plan Review Notes For Permit 14100612 |
| Permit Number |
14100612 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-23 16:59:19 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | A LIFE SAFETY PLAN WAS NOT SUBMITTED WITH THIS PLAN. | | | THE LIFE SAFETY PLAN SHALL INCLUDE THE OCCUPANCY LOADS, | | | EXIT PATHS WITH OCCUPANY LOADS, TRAVEL DISTANCES, ALL | | | EXIT SIGNS, EXITS, EMERGENCY LIGHTS, FIRE EXTIGUISHER | | | LOCATIONS. IT IS EXTREMELY IMPORTANT TO KNOW AND | | | UNDERSTAND HOW PEOPLE AND HOW MANY PEOPLE WILL BE USING | | | EACH EXIT AND GETTING OUT OF THIS MEZZANINE SPACE IN | | | THE EVENT OF A FIRE. | | | | | | SHEET A 2-1, THE PROPOSED REAR EXITING THROUGH PRIVATE | | | ROOM 208 IS NOT APPROVED. THE 4'6" CORRIDOR SHALL BE | | | CONTINUED TO THE LOCKER ROOM DOOR. IT IS RECOMMENDED | | | THAT THE ROOMS BE SHIFTED TO ALLOW THIS HALLWAY | | | CONFIGUATION. (AS HAND DRAWN ON ONE OF SHEET PLANS) | | | | | | SHEET CRV UNDER GENERAL NOTES, REFERENCE SHALL BE MADE | | | THAT A FIRE ALRM IS REQUIRED AND FOR THE FUTURE | | | SUBMITTAL SHOP DRAWINGS. |
|