| 2014-10-21 16:10:54 | 6651 NORTH JOG ROAD - FIRE PUMPS AND CONTROLLERS | | | PERMIT #14100563 | | | MASTER #13080231 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | DRAWINGS INDICATE AN ADDRESS OF 6701 NORTH JOG ROAD | | | (MAINTENANCE BLDG). ADDRESS SHOULD BE 6651 NORTH JOG | | | ROAD (POWER BLOCK BLDG). | | | | | | DRAWING 700-FP-113: DETAIL #6 - PIPING ELEVATIONS, | | | VERIFY 100-INCHES (10 PIPE DIAMETERS) BETWEEN PUMPS' | | | SUCTION FLANGES AND ADJACENT SUCTION PIPE ELBOW OR TEE | | | FITTINGS. (PER NFPA 20 SECTION 5.14.6.3.2, THE DISTANCE | | | OF THE FIRE PUMP SUCTION FLANGE AND ANY ADJACENT | | | SUCTION PIPE ELBOW/TEE FLANGE SHALL BE SEPARATED BY AT | | | LEAST 10 PIPE DIAMETERS WHEN THE ELBOW/TEE HAS A | | | CENTERLINE PLANE PARALLEL TO A HORIZONTAL SPLIT-CASE | | | PUMP SHAFT.) | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | | | | | | | |
|