| 2014-10-30 18:24:16 | RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROPOSED APARTMENT AND GARAGE BUILDING: | | | A) PROVIDE EQUIPMENT SIZING CALCULATIONS WITH THE | | | EQUIPMENT MANUFACTURER'S AND MODEL NUMBER AS REQUIRED | | | BY SEC. 403.6.1 OF 2010 FBC-ENERGY CONSERVATION. NOTE: | | | EQUIPMENT TO MATCH EQUIPMETN LISTED IN THE A/C PLAN. | | | | | | B) PROVIDE COMPLIANCE WITH THE BALANCED RETURN AIR FOR | | | THE BEDROOM AS REQUIRED BY SEC. M1602.4 OF 2010 | | | FBC-RESIDENTIAL. NOTE: THIS IS ONE BEDROOM APARTMENT. | | | SO, IT COUNTS AS A MASTER BEDROOM. SEE EXCEPTION #3 OF | | | SEC. M1602.4 OF 2010 FBC-RESIDENTIAL FOR PROPER DUCT | | | SIZING. | | | | | | 2- MAIN HOUSE: | | | A) PROVIDE EQUIPMENT SIZING CALCULATIONS WITH THE | | | EQUIPMENT MANUFACTURER'S AND MODEL NUMBER AS REQUIRED | | | BY SEC. 403.6.1 OF 2010 FBC-ENERGY CONSERVATION. NOTE: | | | EQUIPMENT TO MATCH EQUIPMETN LISTED IN THE A/C PLAN. | | | | | | B) PROVIDE COMPLIANCE WITH THE BALANCED RETURN AIR FOR | | | ALL THE BEDROOMS AS REQUIRED BY SEC. M1602.4 OF 2010 | | | FBC-RESIDENTIAL. NOTE: SEE EXCEPTION #3 OF SEC. M1602.4 | | | OF 2010 FBC-RESIDENTIAL FOR MASTER BEDROOM PROPER DUCT | | | SIZING. | | | | | | ****NOTE: SEPARATE A/C PERMIT MAY BE REQRUIED FOR EACH | | | BUILDING. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|