| 2014-10-30 17:27:00 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- ARCHITECT OF RECORD TO SPECIFY ALTERATION LEVEL AS |
| | REQUIRED BY SEC. 401.4 OF 2010 FBC-EXISTING BUILDING. |
| | NOTE: KEEP IN MIND CHANGE OF USE FROM GARAGE, STORAGE, |
| | LAUNDRY AND PLAY ROOM (PER CITY RECORDS MAY 29, 1957) |
| | TO ADDITIONAL INDEPENDENT APARTMENT AND GARAGE. |
| | |
| | 2- CONVERSION TO ADDITIONAL DWELLING UNIT REQUIRES |
| | REVIEW BY THE THE PALM BEACH COUNTY FOR IMPACT FEES. |
| | PLEASE BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG |
| | RD) TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY |
| | STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE |
| | UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 3- WINDOWS IN THE PROPOSED BEDROOM DON'T COMPLY WITH |
| | SEC. R310 OF 2010 FBC-RESIDENTIAL. AT LEAST ONE WINDOW |
| | NEEDS TO COMPLY WITH THE MINIMUM WIDTH, HEIGHT AND |
| | TOTAL CLEAR OPENING. REVISE PLANS AS REQUIRED TO |
| | COMPLY. |
| | |
| | 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 101.4.3 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 5- CONSTRUCTION DOCUMENTS TO PROVIDE INFORMATION |
| | SHOWING COMPLIANCE WITH THE ENERGY CODE AS REQUIRED BY |
| | SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | COORDINATE INFORMATION WITH THE ENERGY CALCULATIONS TO |
| | AVOID DELAYS OR CONFLICTS. SPECIFY INSULATION IN ALL |
| | WALLS AND CEILING (INCLUDING EXTERIOR WALLS). NOTE: R19 |
| | INSULATION DOESN'T FIT ON A 2X4 STUD WALL. REVISE AS |
| | REQUIRED. ALSO, CLARIFY WALL TYPE AND STUD SPACING: |
| | WALL LEGEND SAYS METAL STUDS, WHILE WALL SECTION 1B |
| | SAYS WOOD STUDS. REVISE AS REQUIRED TO MATCH. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR THE OVERHEAD GARAGE DOOR AS SHOWN ON |
| | PLANS. |
| | |
| | 7- ARCHITECT TO REVIEW AND APPROVE ABOVE PRODUCT |
| | APPROVAL AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS |
| | TO FBC. |
| | |
| | 8- PARTITION WALL TYPE 1B DETAIL ON SHEET A-2: PROVIDE |
| | SPECS SHOWING HOW IS THE GYPSUM BOARD ATTACHED TO THE |
| | BOTTOM OF THE TRUSSES. THE WAY IT'S DRAWN IT LOOKS LIKE |
| | IT'S SUSPENDED ON THE AIR NOT ATTACHED TO THE TRUSS. |
| | REVISE/CLARIFY DETAIL AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 9- CLARIFY WHY THERE WAS A SEPARATE SIGNED AND SEALED |
| | WINDOW AND DOOR SCHEDULED SUBMITTED?. THIS SCHEDULES |
| | ARE ALREADY SHOWN ON SHEET A-4. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 10- REVISE STRUCTURAL DOORS AND WINDOWS STRUCTURAL BUCK |
| | SHOWN ON SHEET A-4. THE BUCK SIZE NEEDS TO PROVIDE FULL |
| | SUPPORT TO THE DOOR AND WINDOW FRAME AS REQUIRED BY |
| | SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | NOTE: PLANS SUBMITTED ONLY SHOW WORK IN THE REAR |
| | APARTMENT BUILDING. THERE ARE NO PLANS FOR THE MAIN |
| | HOUSE, EXCEPT FOR THE A/C WORK. THERE IS AN EXPIRED |
| | PERMIT APPLICATION DATED FEBRUARY 27, 2014 FOR WORK ON |
| | THE MAIN HOUSE. THIS PERMIT WAS NEVER ISSUED. |
| | |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | *** PLEASE REMOVE AND REPLACE ANY REVISED SHEET. |
| | |