2014-10-16 18:26:16RE-ROOF BUILDING REVIEW COMMENTS
 CODE: 2010 FBC.
  
 1-ENGINEER TO REVISE RAS 117 CALCULATIONS SUBMITTED:
 A) NAILING SPACING FOR ROOF ZONE #3 DOESN'T MEET THE
 DESIGN PRESSURES (-135PSF). RE-RUN THE CALCULATIONS AND
 REVISE NAIL SPACING AS REQUIRED.
  
 B) ENGINEER TO REVISE THE NOA REFERENCED IN THE RAS 117
 CALCULATIONS. SEE COMMENT #2 BELOW. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 2- MODIFIED BITUMEN NOA 12-0716.18 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE
 DOWNLOAD CURRENT NOA AND RE-SUBMIT.
 NEED CURRENT NOA. DCA RULE 9N-3.
  