| Notes |
| Date |
Text |
| 2014-10-16 18:26:16 | RE-ROOF BUILDING REVIEW COMMENTS | | | CODE: 2010 FBC. | | | | | | 1-ENGINEER TO REVISE RAS 117 CALCULATIONS SUBMITTED: | | | A) NAILING SPACING FOR ROOF ZONE #3 DOESN'T MEET THE | | | DESIGN PRESSURES (-135PSF). RE-RUN THE CALCULATIONS AND | | | REVISE NAIL SPACING AS REQUIRED. | | | | | | B) ENGINEER TO REVISE THE NOA REFERENCED IN THE RAS 117 | | | CALCULATIONS. SEE COMMENT #2 BELOW. SEC. 107.2.1 CITY | | | AMENDMENTS TO FBC. | | | | | | 2- MODIFIED BITUMEN NOA 12-0716.18 SUBMITTED WAS | | | SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE | | | DOWNLOAD CURRENT NOA AND RE-SUBMIT. | | | NEED CURRENT NOA. DCA RULE 9N-3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|