2014-10-28 17:50:10PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 BUILDING DENIED
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE TYPE OF CONSTRUCTION ON SHEET CVR SHOULD BE V-B
 AND NOT III-B. 602.3 TYPE III CONSTRUCTION IS THAT TYPE
 OF CONSTRUCTION IN WHICH THE EXTERIOR WALLS ARE OF
 NONCOMBUSTIBLE MATERIALS AND THE INTERIOR BUILDING
 ELEMENTS ARE OF ANY MATERIAL PERMITTED BY THIS CODE.
 FIRE-RETARDANT-TREATED WOOD FRAMING COMPLYING WITH
 SECTION 2303.2 SHALL BE PERMITTED WITHIN EXTERIOR WALL
 ASSEMBLIES OF A 2-HOUR RATING OR LESS.
 602.5 TYPE V CONSTRUCTION IS THAT TYPE OF CONSTRUCTION
 IN WHICH THE STRUCTURAL ELEMENTS, EXTERIOR WALLS AND
 INTERIOR WALLS ARE OF ANY MATERIALS PERMITTED BY THIS
 CODE.
 ALSO SEE TABLE 601 FIRE-RESISTANCE RATING REQUIREMENTS
 FOR BUILDING ELEMENTS (HOURS) AND TABLE 602
 FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS
 BASED ON FIRE SEPARATION DISTANCE.
  
 2) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION
 SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405. FBC ENERGY CONSERVATION - SECT. 103.2.3.2
 CODE COMPLIANCE CERTIFICATION.
 THE BUILDING?S OWNER, THE OWNER?S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
  
 3) IT APPEARS THAT THE 2 X 12 FLOOR JOISTS SHOWN IN
 DETAIL 2 ON SHEET S-1 SHOULD BUTT INTO THE 2 X 12 WALL
 LEDGER SO THAT THE HANGERS ARE ATTACHED TO THE LEDGER.
 THE DETAIL SHOWS THE JOISTS SITTING ON TOP OF THE
 LEDGER. FBC 107.2.1 & R301.1 APPLICATION. BUILDINGS AND
 STRUCTURES, AND ALL PARTS THEREOF, SHALL BE CONSTRUCTED
 TO SAFELY SUPPORT ALL LOADS, INCLUDING DEAD LOADS, LIVE
 LOADS, ROOF LOADS, FLOOD LOADS, AND WIND LOADS AS
 PRESCRIBED BY THIS CODE.
  
 4) THE WOOD FRAME WALLS ARE REQUIRED TO BE FIRE BLOCKED
 WHERE THE HORIZONTAL FLOOR SPACE MEETS THE VERTICAL
 WALL SPACE. R302.11 FIREBLOCKING. IN COMBUSTIBLE
 CONSTRUCTION, FIREBLOCKING SHALL BE PROVIDED TO CUT OFF
 ALL CONCEALED DRAFT OPENINGS (BOTH VERTICAL AND
 HORIZONTAL) AND TO FORM AN EFFECTIVE FIRE BARRIER
 BETWEEN STORIES, AND BETWEEN A TOP STORY AND THE ROOF
 SPACE.
  
 5) SECTION R704 INSPECTION FOR TERMITES. IN ORDER TO
 PROVIDE FOR INSPECTION FOR TERMITE INFESTATION,
 CLEARANCE BETWEEN EXTERIOR WALL COVERINGS AND FINAL
 EARTH GRADE ON THE EXTERIOR OF A BUILDING SHALL NOT BE
 LESS THAN 6 INCHES (152 MM). EXCEPTIONS: 3. A 4-INCH
 (102 MM) INSPECTION SPACE ABOVE PATIO AND GARAGE SLABS
 AND ENTRY AREAS.
  
 6) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW AND
 SIMPSON CONNECTOR SUBMITTALS.
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  
  
  