| Notes |
| Date |
Text |
| 2014-11-01 03:03:10 | 1) 2010 FL. ACCESSIBILITY CODE SECS.212.2 , 212.3 - | | | WHERE SINKS ARE PROVIDED, AT LEAST 5 % , BUT NO FEWER | | | THAN ONE, OF EACH TYPE PROVIDED IN EACH ACCESSIBLE ROOM | | | OR SPACE SHALL COMPLY W/ SEC.606 OF THE FAC. THE BREAK | | | ROOM SINK SHALL ALSO COMPLY. INDICATE ON BOTH SETS OF | | | PLANS WHICH SINKS COMPLY WITH THE ACCESSIBILITY CODE. | | | 2) SHT. A-1 NOTE # 24 STATES "ALL HANDICAPPED LAVS ARE | | | EXISTING- NO NEW WORK." REMOVE THIS NOTE AS ALL LAVS | | | ARE NEW. | | | 3) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. WPB AMEND. | | | TO 2010 FBC SEC.107.3.5.1.3. | | | 4) SIZE ALL VENTS ON THE SANITARY RISER. WPB AMEND. | | | AMED. TO 2010 FBC SEC.107.2.1. | | | 5) SHT. S-1 - SHOW THE SIZE OF THE SCUPPERS ( LXW ) ON | | | THE ROOF. SHOW THE SQUARE FOOTAGE DRAINED BY EACH | | | SCUPPER AND THE SQUARE FOOTAGE OF THE ROOF. WPB AMEND. | | | TO 2010 FBC SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|