| 2014-10-16 16:17:53 | 10/16/2014 |
| | PROJECT: URGENT CARE |
| | PERMIT#: 14100487 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | ELECTRICAL PLAN REVIEW |
| | ACTION: PROVISO |
| | |
| | 1) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 |
| | INNCLUDING SIGNS SHALL HAVE AUTOMATIC CONTROLS TO TURN |
| | OFF AT DAYLIGHT OR WHEN NOT REQUIRED. CONTROLS SHALL BE |
| | PHOTOSENSOR & TIME CLOCK OR ASTRONOMICAL TIME SWITCH. |
| | ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING |
| | PROGRAMING DURING A LOSS OF POWER FOR A MINIMUM OF 10 |
| | HOURS. FBC-E 505.2.4 |
| | |
| | 2) 517.13 GROUNDING OF RECEPTACLES AND FIXED ELECTRICAL |
| | EQUIPMENT IN PATIENT CARE AREAS. WIRING IN PATIENT CARE |
| | AREAS SHALL COMPLY WITH 517.13(A) AND (B). |
| | (A) WIRING METHODS. ALL BRANCH CIRCUITS SERVING PATIENT |
| | CARE AREAS SHALL BE PROVIDED WITH AN EFFECTIVE |
| | GROUND-FAULT CURRENT PATH BY INSTALLATION IN A METAL |
| | RACEWAY SYSTEM, OR A CABLE HAVING A METALLIC ARMOR OR |
| | SHEATH ASSEMBLY. THE METAL RACEWAY SYSTEM, OR METALLIC |
| | CABLE ARMOR, OR SHEATH ASSEMBLY SHALL ITSELF QUALIFY AS |
| | AN EQUIPMENT GROUNDING CONDUCTOR IN ACCORDANCE WITH |
| | 250.118. |
| | (B) INSULATED EQUIPMENT GROUNDING CONDUCTOR. THE |
| | GROUNDING TERMINALS OF ALL RECEPTACLES AND ALL |
| | NON?CURRENT CARRYING CONDUCTIVE SURFACES OF FIXED |
| | ELECTRICAL EQUIPMENT LIKELY TO BECOME ENERGIZED THAT |
| | ARE SUBJECT TO PERSONAL CONTACT, OPERATING AT OVER 100 |
| | VOLTS, SHALL BE CONNECTED TO AN INSULATED COPPER |
| | EQUIPMENT GROUNDING CONDUCTOR. THE EQUIPMENT GROUNDING |
| | CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE |
| | 250.122 AND INSTALLED IN METAL RACEWAYS OR AS A PART OF |
| | LISTED CABLES HAVING A METALLIC ARMOR OR SHEATH |
| | ASSEMBLY WITH THE BRANCH-CIRCUIT CONDUCTORS SUPPLYING |
| | THESE RECEPTACLES OR FIXED EQUIPMENT. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |