| 2015-06-12 17:58:54 | W. P. B. BUILDING PLAN REVIEW |
| | REVISION: 14100419 |
| | PERMIT: 14060978 |
| | ADD: 1501 NORTHPOINT PARKWAY # 100 |
| | CONT:DAVID JOYNER CONSTRUCTION |
| | TEL: (561)965-3795 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: FRI. JUNE 12/2015 |
| | ACTION: DENIED |
| | |
| | 1-6) COMPLIED. |
| | |
| | 7) THE NEW PLANS SHOW A TRUE STEEL FRAMED SECOND FLOOR, |
| | STAIRS GUARDRAIL & HANDRAIL ASSEMBLY. THIS TYPE OF |
| | BUILDING REQUIRES A ON-SITE RESIDENT INSPECTOR. |
| | |
| | 7A) COMPLIED. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING |
| | OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE |
| | INSPECTIONS REQUIRED BY SECTION 109. RESIDENT INSPECTOR |
| | FORMS RETURNED FILLED OUT. |
| | |
| | 7B)SEMI-COMPLIED. 3RD REQUEST. . THE RESUME' MUST BE |
| | ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED HEREIN. |
| | FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME' |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 7C)3RD REQUEST. RESPONSE INDICATES THE ABOVE |
| | INFORMATION HAS BEEN SUBMITTED BY THE RESIDENT |
| | INSPECTOR ENGINEER. NOT IN THE PACKAGE |
| | THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO |
| | KEN CONRAD BY E-MAIL. KEN CONRAD: [email protected] |
| | RESIDENT INSPECTOR FORMS WILL BE E-MAILED TO: |
| | [email protected] |
| | |
| | 7D) 3RD REQUEST. PLEASE NOTE(3) SETS OF PLANS ARE |
| | REQUIRED. THERE IS (2) REVISED DENIED PLANS DATED |
| | 3/26/15 BY ARCHITECT JAMES STORM, ONE SET OF THE |
| | CONTRACTORS ISSUED PLANS WHY WERE THEY SUBMITTED, THEY |
| | ARE TO REMAIN AT THE JOBSITE FOR INSPECTION PURPOSES. |
| | NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE REQUIRED. |
| | FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE PERMIT |
| | LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND BATCH |
| | STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF |
| | PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE |
| | RESIDENT INSPECTOR, THE OTHER FOR THE MEP INSPECTORS. |
| | |
| | 7E) NOTICE ONLY!!! PLEASE CALL THE CITY OF WEST PALM |
| | BEACHES? AUTOMATED TELEPHONE INSPECTIONS LINE (561) |
| | 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF |
| | JOBSITE INSPECTIONS. |
| | |
| | 8) COMPLIED. THE SUBMITTED 2ND FLOOR STRUCTURAL PLAN BY |
| | COGAN WIRE & METAL PRODUCTS HAS NOT BEEN REVIEWED BY |
| | THE DESIGNER OF RECORD, WILL REQUIRE THERE SHOP DRAWING |
| | STAMP OF APPROVAL. FL 61G1-23.015 (2) THE ARCHITECT IS |
| | RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT |
| | DATA, REPORTS, SHOP DRAWINGS ETC... |
| | |
| | 9) THE PLANS FROM COGAN WIRE AND METAL PRODUCTS HAS |
| | NOTES: |
| | 9A) 3RD REQUEST. THE RESPONSE INDICATES THE STRUCTURAL |
| | ENGINEER HAS REVIEWED THE LOADING OF THE SLAB, PLEASE |
| | PROVIDE THE ENGINEERS LETTER SIGNED AND SEALED DOCUMENT |
| | STATING SUCH. THE MAXIMUM UNFACTORED AXIAL LOAD APPLIED |
| | ON THE SLAB BY A COLUMN IS 26,600 LBS. |
| | |
| | 9B) 3RD REQUEST. RESPONSE IS THE OWNER HAS OBTAINED THE |
| | SERVICES OF A REGISTERED ENGINEER FOR THIS ANALYSIS. |
| | PLEASE PROVIDE THE SIGNED AND SEALED DOCUMENT FOR THE |
| | STRUCTURAL ANALYSIS ON THE SLAB AND OR FOUNDATION. |
| | THE CAPACITY OF THE SLAB AND OR FOUNDATION MUST BE |
| | VERIFIED BY THE CLIENT AND OR THE OWNER. |
| | |
| | 10) COMPLIED. ALL SHOP DRAWINGS THAT WILL DEAL WITH THE |
| | STEEL 2ND FLOOR AND SUPPORTING SYSTEM ARE REQUIRED TO |
| | BE REVIEWED BY THE DESIGNER OF RECORD BEFORE SUBMITTAL |
| | TO THE BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | 11) NEW COMMENT, THE COVERSHEET STATES THERE IS A MIXED |
| | USE OCCUPANCY BUSINESS AND S-1 MODERATE HAZARD YET |
| | THERE IS NO OCCUPANCY SEPARATION BETWEEN THE 2 |
| | OCCUPANCIES. THERE SHOULD BE A (1) HOUR FIRE SEPARATION |
| | BETWEEN THE 2 OCCUPANCIES. SEE TABLE 508.4, THIS TABLE |
| | HAS BEEN BACKWARDS ON THE S1/ S2 CLASSIFICATION SINCE |
| | THE CONCEPTION OF THIS TABLE IN THE 2007 FBC-B. PLEASE |
| | SEE BOAF INFORMAL INTERPRETATION 7357 JULY 1/2014. |
| | 12) NEW COMMENT. THE NEW STORAGE OCCUPANCY 2ND FLOOR, |
| | PLEASE PROVIDE FROM THE TRAVEL DISTANCE FROM THE MOST |
| | REMOTE POINT OF THE 2ND FLOOR STORAGE OCCUPANCY, DOWN |
| | THE OPEN STAIRS AND OUT OF THE BUILDING TO THE EXIT |
| | DISCHARGE PER FBC-B 1016.1 EXCEPTION 4 AND TABLE |
| | 1016.1. |
| | 13) NEW COMMENT. PLEASE BE ADVISED REVISIONS WILL ALSO |
| | BE REQUIRED BECAUSE OF SITE VIOLATIONS FOUND BY FIELD |
| | VISITS FROM BOTH THE FIRE DEPARTMENT AND BUILDING |
| | DEPARTMENT. |
| | 14) THE NEW 2ND FLOOR AREA OF 2,668 SQ, FT, WILL NEED |
| | TO BE REVIEWED BY PAL BEACH COUNTY IMPACT FEE OFFICE. |
| | IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERRMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |