Plan Review Notes
Plan Review Notes For Permit 14100419
Permit Number 14100419
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2015-04-09 16:33:201501 NORTHPOINT PARKWAY, SUITE #100
 TRACKING #14100419
 MASTER #14060978
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: A SITE VISIT WAS PERFORMED 04/09/15
  
  
 PER NFPA 101 CHAPTER 39 - EXISTING BUSINESS OCCUPANCIES
 THE TWO STAIR CASES LOCATED IN THE BUSINESS (OFFICE
 AREAS) OCCUPANCY WILL NEED TO BE COMPLETELY ENCLOSED
 TOP/BOTTOM BY A 1-HOUR FIRE RATING WITH FIRE RATED
 OPENINGS/DOORS PER NFPA 101 SECTION 39.3.1 PROTECTION
 OF VERTICAL OPENINGS. PER 39.3.1.1 VERTICAL OPENINGS
 SHALL BE ENCLOSED OR PROTECTED IN ACCORDANCE WITH
 SECTION 8.6 (COMMUNICATING SPACE, ATRIUM, MEZZANINE OR
 CONVENIENCE OPENING). PER 39.2.4 NUMBER OF MEANS OF
 EGRESS (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 PROVIDED ON EVERY STORY.
  
 THE STORAGE OCCUPANCY NEEDS TO BE SEPARATED
 (HORIZONTALLY, VERTICALLY, OR BOTH) FROM THE BUSINESS
 OCCUPANCY BY A 1-HOUR FIRE RATING. PER SECTION 8.3.5.1,
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 PROVIDE A PROPOSED STORAGE LAYOUT FOR THE LARGE
 WAREHOUSE SPACE. INDICATE WHAT, WHERE, HOW IT WILL ALL
 BE STORED.
  
 PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE
 AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 THE NW CORRIDOR OF THE FIRST FLOOR IN THE BUSINESS
 OCCUPANCY CREATES A DEAD-END BECAUSE THE BUSINESS
 OCCUPANCY IS NOT PERMITTED TO EXIT THROUGH THE STORAGE
 OCCUPANCY.
  
 ADDITIONAL EMERGENCY LIGHTING NEEDED THROUGHOUT BOTH
 THE STORAGE AND BUSINESS OCCUPANCY. EMERGENCY
 ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM OF 1.5
 HOURS IN THE EVENT OF FAILURE OF NORMAL LIGHTING.
 EMERGENCY LIGHTING FACILITIES SHALL BE ARRANGED TO
 PROVIDE INITIAL ILLUMINATION THAT IS NOT LESS THAN AN
 AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, NOT LESS THAN
 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT
 FLOOR LEVEL.
  
 WEST STAIR: GUARDS, AT LEAST 42-INCHES TALL, SHALL BE
 PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS (STAIRS,
 MEZZANINE, ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR.
 OPEN GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH
 DIAMETER SPHERE UP TO A HEIGHT OF 34-INCHES. THE
 TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD AND
 BOTTOM ELEMENT OF THE GUARDRAIL SHALL PROHIBIT THE
 PASSAGE OF A 6-INCH DIAMETER SPHERE.
  
 WEST STAIR: HANDRAIL IS NOT CONTINUOUSLY GRASPABLE
 ALONG THE LOWER STAIR STRINGER.
  
 EAST STAIR: HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE
 STAIR. HANDRAILS SHALL BE LOCATED NOT LESS THAN 34
 INCHES AND NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF
 THE TREAD, MEASURED VERTICALLY TO THE TOP OF THE RAIL
 FROM THE LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL
 BE RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES.
  
 FIRE ALARM: THE FIRE ALARM SYSTEM IS DATED, DOES NOT
 HAVE ANY CAPACITY FOR ADDING NEW DEVICES AND DOES NOT
 APPEAR TO MEET THE AUDIBLE/VISIBLE REQUIREMENTS OF NFPA
 72. SEVERAL COMMON/PUBLIC SPACES HAVE NO FIRE ALARM
 NOTIFICATION DEVICES.
  
 NO ADA ACCESSIBILITY (ELEVATOR/LULA LIFT) TO THE SECOND
 FLOOR.
  
 SEPARATE PLANS AND PERMITS NEEDED FOR FIRE ALARM AND
 FIRE SPRINKLER ALTERATIONS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  