Plan Review Notes
Plan Review Notes For Permit 14100419
Permit Number 14100419
Review Stop E
Sequence Number 2
Notes
Date Text
2015-06-25 10:18:016/25/2015
 PROJECT: NORTHPOINT SUITE 100
 PERMIT#: 14100419
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) DUPLICATE COMMENT: 1ST FLOOR
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT
 (EMERGENCY AND EXIT LIGHTING) SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN THE AREA
 AND CONNECTED AHEAD OF ANY LOCAL SWITCHES. NEC 700.12
 THE NOTE WAS ADDED TO PG 6.1 HOWEVER THERE IS STILL A
 CONFLICT. CIRCUIT 1 ON PANEL SCHEDULE PANEL HA IS
 IDENTIFIED AS THE NIGHT LIGHT CIRCUIT.
 THE 1ST FLOOR PLAN INDICATE CIRCUIT HA1 IS THE CIRCUIT
 TO BE USED TO ENERGIZE EMERGENCY AND EXIT LIGHTING AND
 THE GENERAL LIGHTING IN THAT SAME AREA IS IDENTIFIED AS
 CIRCUIT HA26 A LIGHTS AND HA28 B LIGHHTS.
  
 2) 2ND FLOOR:
 EMERGENCY AND EXIT LIGHTING HAS BEEN ADDED BUT THE
 CIRCUITRY TO FEED IT IS NOT CLEAR. THE LIGHTING
 CIRCUITS ARE IDENTIFIED ON THE FLOOR PLAN BUT THE
 EMERGENCY AND EXIT LIGHTS CIRCUITS ARE NOT IDENTIFED
 ANYWHERE EXCEPT IN PANEL HA AS CIRCUIT HA1 WHICH IS NOT
 EVEN THE SAME SYSTEM VOLTAGE LET ALONE THE SAME
 CIRCUIT. CLARIFY WHAT CIRCUITS ARE INTENDED TO FEED
 LIGHTING AND THE EMERGENCY AND EXIT EGRESS FIXTURES.
  
 3) THE DRINKING FOUNTAIN IS IDENTIFIED AS CIRCUIT LD
 22. ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GROUND FAULT CIRCUIT INTERRUPTER PROTECTION. NEC
 422.52.
 INDICATE ON THE PLAN THIS CIRCUIT IS PROTECTED WITH A
 GFCI DEVICE.
  
 4) MODULAR FURNITURE CUBICALS HAVE BEEN ADDED TO THE
 FLOOR PLAN. INDICATE THE CIRCUITS FEEDING THE MODULAR
 FURNITURE IS INSTALLED IN COMPLIANCE WITH THE NEC 605
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  