| | PROJECT: NORTHPOINT SUITE 100 |
| | PERMIT#: 14100419 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) DUPLICATE COMMENT: 1ST FLOOR |
| | THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT |
| | (EMERGENCY AND EXIT LIGHTING) SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN THE AREA |
| | AND CONNECTED AHEAD OF ANY LOCAL SWITCHES. NEC 700.12 |
| | THE NOTE WAS ADDED TO PG 6.1 HOWEVER THERE IS STILL A |
| | CONFLICT. CIRCUIT 1 ON PANEL SCHEDULE PANEL HA IS |
| | IDENTIFIED AS THE NIGHT LIGHT CIRCUIT. |
| | THE 1ST FLOOR PLAN INDICATE CIRCUIT HA1 IS THE CIRCUIT |
| | TO BE USED TO ENERGIZE EMERGENCY AND EXIT LIGHTING AND |
| | THE GENERAL LIGHTING IN THAT SAME AREA IS IDENTIFIED AS |
| | CIRCUIT HA26 A LIGHTS AND HA28 B LIGHHTS. |
| | |
| | 2) 2ND FLOOR: |
| | EMERGENCY AND EXIT LIGHTING HAS BEEN ADDED BUT THE |
| | CIRCUITRY TO FEED IT IS NOT CLEAR. THE LIGHTING |
| | CIRCUITS ARE IDENTIFIED ON THE FLOOR PLAN BUT THE |
| | EMERGENCY AND EXIT LIGHTS CIRCUITS ARE NOT IDENTIFED |
| | ANYWHERE EXCEPT IN PANEL HA AS CIRCUIT HA1 WHICH IS NOT |
| | EVEN THE SAME SYSTEM VOLTAGE LET ALONE THE SAME |
| | CIRCUIT. CLARIFY WHAT CIRCUITS ARE INTENDED TO FEED |
| | LIGHTING AND THE EMERGENCY AND EXIT EGRESS FIXTURES. |
| | |
| | 3) THE DRINKING FOUNTAIN IS IDENTIFIED AS CIRCUIT LD |
| | 22. ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH |
| | GROUND FAULT CIRCUIT INTERRUPTER PROTECTION. NEC |
| | 422.52. |
| | INDICATE ON THE PLAN THIS CIRCUIT IS PROTECTED WITH A |
| | GFCI DEVICE. |
| | |
| | 4) MODULAR FURNITURE CUBICALS HAVE BEEN ADDED TO THE |
| | FLOOR PLAN. INDICATE THE CIRCUITS FEEDING THE MODULAR |
| | FURNITURE IS INSTALLED IN COMPLIANCE WITH THE NEC 605 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |