| 2015-04-06 11:03:53 | W. P. B. BUILDING PLAN REVIEW |
| | REVISION: 14100419 |
| | PERMIT: 14060978 |
| | ADD: 1501 NORTHPOINT PARKWAY # 100 |
| | CONT:DAVID JOYNER CONSTRUCTION |
| | TEL: (561)965-3795 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. APRIL 06/2015 |
| | ACTION: DENIED |
| | |
| | 1-6) COMPLIED. |
| | |
| | 7) THE NEW PLANS SHOW A TRUE STEEL FRAMED SECOND FLOOR, |
| | STAIRS GAURDRAIL & HANDRAIL ASSEMBLY. THIS TYPE OF |
| | BUILDING REQUIRES A ON-SITE RESIDENT INSPECTOR. |
| | |
| | 7A) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| | INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| | OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| | BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| | OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| | INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| | QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| | FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| | BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| | AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| | THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| | AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| | |
| | 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| | 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F ?C) IN EXCESS OF 3000 |
| | POUNDS PER SQUARE INCH |
| | 4. FOR PILE DRIVING |
| | 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| | FOOT |
| | 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| | 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| | METHODS OF CONSTRUCTION |
| | |
| | 7B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 7C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| | SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| | [email protected] |
| | RESIDENT INSPECTOR FORMS WILL BE E-MAILED TO: |
| | [email protected] |
| | |
| | 7D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE |
| | PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND |
| | BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO |
| | SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR |
| | THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP |
| | INSPECTORS. |
| | |
| | 7E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 8) THE SUBMITTED 2ND FLOOR STRUCTURAL PLAN BY COGAN |
| | WIRE & METAL PRODUCTS HAS NOT BEEN REVIEWED BY THE |
| | DESIGNER OF RECORD, WILL REQUIRE THERE SHOP DRAWING |
| | STAMP OF APPROVAL. FL 61G1-23.015 (2) THE ARCHITECT IS |
| | RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT |
| | DATA, REPORTS, SHOP DRAWINGS ETC... |
| | |
| | 9) THE PLANS FROM COGAN WIRE AND METAL PRODUCTS HAS |
| | NOTES: |
| | 9A) THE MAXIMUM UNFACTORED AXIAL LOAD APPLIED ON THE |
| | SLAB BY A COLUMN IS 26,600 LBS. |
| | |
| | 9B) THE CAPACITY OF THE SLAB AND OR FOUNDATION MUST BE |
| | VERIFIED BY THE CLIENT AND OR THE OWNER. |
| | |
| | 10) ALL SHOP DRAWINGS THAT WILL DEAL WITH THE STEEL 2ND |
| | FLOOR AND SUPPORTING SYSTEM ARE REQUIRED TO BE REVIEWED |
| | BY THE DESIGNER OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | |
| | 11) THE NEW 2ND FLOOR AREA OF 2,668 SQ, FT, WILL NEED |
| | TO BE REVIEWED BY PAL BEACH COUNTY IMPACT FEE OFFICE. |
| | IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |