2014-10-16 15:19:421501 NORTHPOINT PARKWAY, SUITE #100
 TRACKING #14100419
 MASTER #14060978
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DOES THIS PERMIT REVISION OF ADDING 2 MEZZANINES
 INCREASE THE PERMIT VALUE OF THE MASTER PERMIT
 #14060978?
  
 NO ADDRESS PROVIDED ON PLANS.
  
 PROVIDE A COMPLETE FLOOR PLAN SHOWING THE MEZZANINE IN
 RELATION TO THE MAIN FLOOR. INDICATE THE SIZE/SQUARE
 FOOTAGE OF THE MEZZANINES.
  
 PROVIDE A LIFE SAFETY PLAN INDICATING OCCUPANCY TYPE,
 OCCUPANT LOADS, COMMON PATH OF TRAVEL DISTANCES, TRAVEL
 DISTANCE TO EXITS, LIGHTING, EXIT SIGNS, EMERGENCY
 LIGHTING, ETC.
  
 DESIGN SHALL CONFORM TO THE REQUIREMENTS OF NFPA 101
 SECTION 8.6.9 FOR MEZZANINES.
  
 THE AGGREGATE AREA OF MEZZANINES LOCATED WITHIN A ROOM,
 OTHER THAN THOSE LOCATED IN SPECIAL-PURPOSE INDUSTRIAL
 OCCUPANCIES, SHALL NOT EXCEED ONE-THIRD THE OPEN AREA
 OF THE ROOM IN WHICH THE MEZZANINES ARE LOCATED.
 ENCLOSED SPACE SHALL NOT BE INCLUDED IN A DETERMINATION
 OF THE SIZE OF THE ROOM IN WHICH THE MEZZANINE IS
 LOCATED. FOR PURPOSES OF DETERMINING THE ALLOWABLE
 MEZZANINE AREA, THE AGGREGATE AREA OF THE MEZZANINES
 SHALL NOT BE INCLUDED IN THE AREA OF THE ROOM.
  
 ALL PORTIONS OF A MEZZANINE, OTHER THAN WALLS NOT MORE
 THAN 42-INCHES HIGH, COLUMNS, AND POSTS, SHALL BE OPEN
 TO AND UNOBSTRUCTED FROM THE ROOM IN WHICH THE
 MEZZANINE IS LOCATED, UNLESS THE OCCUPANT LOAD OF THE
 AGGREGATE AREA OF THE ENCLOSED SPACE DOES NOT EXCEED
 10. A MEZZANINE HAVING TWO OR MORE MEANS OF EGRESS
 SHALL NOT BE REQUIRED TO OPEN INTO THE ROOM IN WHICH IT
 IS LOCATED IF NOT LESS THAN ONE OF THE MEANS OF EGRESS
 PROVIDES DIRECT ACCESS FROM THE ENCLOSED AREA TO AN
 EXIT AT THE MEZZANINE LEVEL.
  
 GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT
 THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE,
 ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN
 GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER
 SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR
 OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT
 OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH
 DIAMETER SPHERE.
  
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR.
 HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND
 NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD,
 MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE
 LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE
 RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 INDICATE IF THE BUILDING IS PROTECTED BY AUTOMATIC
 SPRINKLERS OR A FIRE ALARM SYSTEM. SEPARATE PLANS AND
 PERMITS WILL BE NEEDED TO ACCOUNT FOR THE MEZZANINES.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  
  