| Plan Review Notes For Permit 14100419 |
| Permit Number |
14100419 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-10 13:17:13 | 1) SEE FIRE DEPT. COMMENTS REGARDING EMERGENCY | | | LIGHTING. | | | 2) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL | | | BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL | | | SWITCHES. NEC 700.12 | | | 4) EMERGENCY LIGHTING SYSTEMS SHALL BE DESIGNED AND | | | INSTALLED SO THAT THE FAILURE OF ANY INDIVIDUAL | | | LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF A LAMP, | | | CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT REQUIRES | | | EMERGENCY ILLUMINATION. NEC 700.16 | | | 5) INDICATE CIRCUIT NUMBERS ON THE FLOOR PLAN. | | | |
|