| 2014-10-29 15:08:55 | BUILDING PLAN REVIEW |
| | REVISION: 14100419 |
| | PERMIT: 14060978 |
| | ADD: 1501 NORTHPOINT PARKWAY # 100 |
| | CONT:DAVID JOYNER CONSTRUCTION |
| | TEL: (561)965-3795 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. OCT. 29/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) THE REVISION FORM & PLANS INDICATE THE ADDITIONAL |
| | WORK TO BE COVERED UNDER THIS PERMIT AS ADDING (2) |
| | MEZZANINES IN (2) A/C ROOMS. PLEASE PROVIDE A OVER ALL |
| | FLOOR PLAN WHERE THESE MEZZANINES WILL BE ADDED. PLEASE |
| | ALSO CLARIFY THE USAGE OF THE (2) A/C ROOMS WHERE THE |
| | MEZZANINES WILL BE ADDED. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 2) THE FLOOR PLAN SHALL SHOW THE ROOM IN WHICH THE |
| | MEZZANINES ARE TO BE BUILT, PLEASE PROVIDE CODE |
| | COMPLIANCE WITH 2010 FBC-B 505.2 AREA LIMITATIONS AND |
| | IF EXCEPTION 1 OR 2 ARE BEING TAKEN , THIS BEING A |
| | BUILDING TYPE IIA/ SPRINKLERED. |
| | |
| | 3) PLEASE PROVIDE THE OCCUPANCY TYPE AND OCCUPANCY |
| | LOADS FOR EACH MEZZANINE AREA COMPLY WITH 2010 FBC-B |
| | 505.3. |
| | |
| | 4) THE PLANS CURRENTLY DO NOT PROVIDE ENOUGH DETAIL FOR |
| | WITHIN THE ROOMS TO SHOW COMPLIANCE WITH 2010 FBC-B |
| | 505.4. |
| | |
| | 5) THE BUILDING THE MEZZANINE IS GOING TO BE INSTALLED |
| | IN IS A FIRE SPRINKLERED BUILDING ARE THERE GOING TO |
| | HAVE FIRE SPRINKLERS UNDER THE MEZZANINE LEVEL TO |
| | PROTECT THE FIRE LOADS BELOW THE MEZZANINE? F] 505.5.2 |
| | FIRE SUPPRESSION. |
| | WHERE LOCATED IN A BUILDING THAT IS REQUIRED TO BE |
| | PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM, EQUIPMENT |
| | PLATFORMS SHALL BE FULLY PROTECTED BY SPRINKLERS ABOVE |
| | AND BELOW THE PLATFORM, WHERE REQUIRED BY THE STANDARDS |
| | REFERENCED IN SECTION 903.3. |
| | |
| | 6) THE PLANS (14060978) INDICATE THIS TO BE A BUILDING |
| | TYPE IIA BUILDING, PLEASE SHOW HOW COMPLIANCE WILL BE |
| | ACHIEVED WITH TABLE 601 FIRE-RESISTANCE RATING |
| | REQUIREMENTS FOR BUILDING ELEMENTS (HOURS), FLOOR |
| | CONSTRUCTION AND SECONDARY MEMBERS. |
| | |
| | PLEASE NOTE THE PLANS DO INDICATE BOTH THE FLOOR AND |
| | LANDING ARE OPEN BAR GRATING IF THE MEZZANINE IS LARGER |
| | THAN ALLOWED BY 505.2 THE DESIGNER OF RECORD MAY WANT |
| | TO ASK THE BUILDING OFFICIAL TO CONSIDER THIS UNDER |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 104.11 ALTERNATIVE |
| | MATERIALS, DESIGN AND METHODS OF CONSTRUCTION AND |
| | EQUIPMENT. THE PROVISIONS OF THIS CODE ARE NOT INTENDED |
| | TO PREVENT THE INSTALLATION OF ANY MATERIAL OR TO |
| | PROHIBIT ANY DESIGN OR METHOD OF CONSTRUCTION NOT |
| | SPECIFICALLY PRESCRIBED BY THIS CODE, PROVIDED THAT |
| | ANY SUCH ALTERNAT IVE HAS BEEN APPROVED. AN ALTERNATIVE |
| | MATERIAL, DESIGN OR METHOD OF CONSTRUCTION SHALL BE |
| | APPROVED WHERE THE BUILDING OFFICIAL FINDS THAT THE |
| | PROPOSED DESIGN IS SATISFACTORY AND COMPLIES WITH THE |
| | INTENT OF THE PROVISIONS OF THIS CODE, AND THAT THE |
| | MATERIAL, METHOD OR WORK OFFERED IS, FOR THE PURPOSE |
| | INTENDED, AT LEAST THE EQUIVALENT OF THAT PRESCRIBED IN |
| | THIS CODE IN QUALITY, STRENGTH, EFFECTIVENESS, FIRE |
| | RESISTANCE, DURABILITY AND SAFETY. WHEN ALTERNATE LIFE |
| | SAFETY SYSTEMS ARE DESIGNED, THE SFPE ENGINEERING GUIDE |
| | TO PERFORMANCE-BASED FIRE PROTECTION ANALYSIS AND |
| | DESIGN OF BUILDINGS, OR OTHER METHODS APPROVED BY THE |
| | BUILDING OFFICIAL MAY BE USED. THE BUILDING OFFICIAL |
| | SHALL REQUIRE THAT SUFFICIENT EVIDENCE OR PROOF BE |
| | SUBMITTED TO SUBSTANTIATE ANY CLAIM MADE REGARDING THE |
| | ALTERNATIVE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |