Plan Review Notes
Plan Review Notes For Permit 14100419
Permit Number 14100419
Review Stop B
Sequence Number 1
Notes
Date Text
2014-10-29 15:08:55BUILDING PLAN REVIEW
 REVISION: 14100419
 PERMIT: 14060978
 ADD: 1501 NORTHPOINT PARKWAY # 100
 CONT:DAVID JOYNER CONSTRUCTION
 TEL: (561)965-3795
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. OCT. 29/ 2014
 ACTION: DENIED
  
 1) THE REVISION FORM & PLANS INDICATE THE ADDITIONAL
 WORK TO BE COVERED UNDER THIS PERMIT AS ADDING (2)
 MEZZANINES IN (2) A/C ROOMS. PLEASE PROVIDE A OVER ALL
 FLOOR PLAN WHERE THESE MEZZANINES WILL BE ADDED. PLEASE
 ALSO CLARIFY THE USAGE OF THE (2) A/C ROOMS WHERE THE
 MEZZANINES WILL BE ADDED.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2) THE FLOOR PLAN SHALL SHOW THE ROOM IN WHICH THE
 MEZZANINES ARE TO BE BUILT, PLEASE PROVIDE CODE
 COMPLIANCE WITH 2010 FBC-B 505.2 AREA LIMITATIONS AND
 IF EXCEPTION 1 OR 2 ARE BEING TAKEN , THIS BEING A
 BUILDING TYPE IIA/ SPRINKLERED.
  
 3) PLEASE PROVIDE THE OCCUPANCY TYPE AND OCCUPANCY
 LOADS FOR EACH MEZZANINE AREA COMPLY WITH 2010 FBC-B
 505.3.
  
 4) THE PLANS CURRENTLY DO NOT PROVIDE ENOUGH DETAIL FOR
 WITHIN THE ROOMS TO SHOW COMPLIANCE WITH 2010 FBC-B
 505.4.
  
 5) THE BUILDING THE MEZZANINE IS GOING TO BE INSTALLED
 IN IS A FIRE SPRINKLERED BUILDING ARE THERE GOING TO
 HAVE FIRE SPRINKLERS UNDER THE MEZZANINE LEVEL TO
 PROTECT THE FIRE LOADS BELOW THE MEZZANINE? F] 505.5.2
 FIRE SUPPRESSION.
 WHERE LOCATED IN A BUILDING THAT IS REQUIRED TO BE
 PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM, EQUIPMENT
 PLATFORMS SHALL BE FULLY PROTECTED BY SPRINKLERS ABOVE
 AND BELOW THE PLATFORM, WHERE REQUIRED BY THE STANDARDS
 REFERENCED IN SECTION 903.3.
  
 6) THE PLANS (14060978) INDICATE THIS TO BE A BUILDING
 TYPE IIA BUILDING, PLEASE SHOW HOW COMPLIANCE WILL BE
 ACHIEVED WITH TABLE 601 FIRE-RESISTANCE RATING
 REQUIREMENTS FOR BUILDING ELEMENTS (HOURS), FLOOR
 CONSTRUCTION AND SECONDARY MEMBERS.
  
 PLEASE NOTE THE PLANS DO INDICATE BOTH THE FLOOR AND
 LANDING ARE OPEN BAR GRATING IF THE MEZZANINE IS LARGER
 THAN ALLOWED BY 505.2 THE DESIGNER OF RECORD MAY WANT
 TO ASK THE BUILDING OFFICIAL TO CONSIDER THIS UNDER
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 104.11 ALTERNATIVE
 MATERIALS, DESIGN AND METHODS OF CONSTRUCTION AND
 EQUIPMENT. THE PROVISIONS OF THIS CODE ARE NOT INTENDED
 TO PREVENT THE INSTALLATION OF ANY MATERIAL OR TO
 PROHIBIT ANY DESIGN OR METHOD OF CONSTRUCTION NOT
 SPECIFICALLY PRESCRIBED BY THIS CODE, PROVIDED THAT
 ANY SUCH ALTERNAT IVE HAS BEEN APPROVED. AN ALTERNATIVE
 MATERIAL, DESIGN OR METHOD OF CONSTRUCTION SHALL BE
 APPROVED WHERE THE BUILDING OFFICIAL FINDS THAT THE
 PROPOSED DESIGN IS SATISFACTORY AND COMPLIES WITH THE
 INTENT OF THE PROVISIONS OF THIS CODE, AND THAT THE
 MATERIAL, METHOD OR WORK OFFERED IS, FOR THE PURPOSE
 INTENDED, AT LEAST THE EQUIVALENT OF THAT PRESCRIBED IN
 THIS CODE IN QUALITY, STRENGTH, EFFECTIVENESS, FIRE
 RESISTANCE, DURABILITY AND SAFETY. WHEN ALTERNATE LIFE
 SAFETY SYSTEMS ARE DESIGNED, THE SFPE ENGINEERING GUIDE
 TO PERFORMANCE-BASED FIRE PROTECTION ANALYSIS AND
 DESIGN OF BUILDINGS, OR OTHER METHODS APPROVED BY THE
 BUILDING OFFICIAL MAY BE USED. THE BUILDING OFFICIAL
 SHALL REQUIRE THAT SUFFICIENT EVIDENCE OR PROOF BE
 SUBMITTED TO SUBSTANTIATE ANY CLAIM MADE REGARDING THE
 ALTERNATIVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]