| Plan Review Notes For Permit 14100394 |
| Permit Number |
14100394 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-24 10:11:06 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | GAS REVIEW IS DENIED. | | | | | | 1) SUBMIT TWO SETS OF A GAS RISER DIAGRAM OR APPLY FOR | | | GAS UNDER A SEPARATE PERMIT. FBC 107.3.5.3 | | | | | | 2) FBC FUEL GAS [M] 614.5 MAKEUP AIR. INSTALLATIONS | | | EXHAUSTING MORE THAN 200 CFM (0.09 M3/S) SHALL BE | | | PROVIDED WITH MAKEUP AIR. WHERE A CLOSET IS DESIGNED | | | FOR THE INSTALLATION OF A CLOTHES DRYER, AN OPENING | | | HAVING AN AREA OF NOT LESS THAN 100 SQUARE INCHES (645 | | | MM2) FOR MAKEUP AIR SHALL BE PROVIDED IN THE CLOSET | | | ENCLOSURE, OR MAKEUP AIR SHALL BE PROVIDED BY OTHER | | | APPROVED MEANS. | | | | | | |
|