| 2014-10-28 09:49:49 | 10/28/2014 |
| | PROJECT: MORANO RESIDENCE |
| | PERMIT#: 14100394 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE A LIGHTING FIXTURE SCHEDULE INDICATING |
| | COMPLIANCE WITH THE FBC-R 402.4.5 RECESSED LIGHTING. |
| | AND FBC-R 404.1 LIGHTING EQUIPMENT. RECESSED LUMINAIRES |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE |
| | SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND |
| | UNCONDITIONED SPACES. A MINIMUM OF 50 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICIENCY. |
| | |
| | 2) PROVIDE THE LIGHTING PACKAGE SUBMITTALS TO ENSURE |
| | COMPLIANCE WITH THE LISTING REQUIREMENTS OF THE NEC |
| | 110.3(B) |
| | |
| | 3) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES |
| | INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| | INCLUDING GARAGE DOOR OPENER OUTLETS, SHALL HAVE GROUND |
| | FAULT CIRCUIT INTERRUPTER PROTECTION FOR PERSONNEL. NEC |
| | 210.8. |
| | |
| | 4) CHECK TOTAL LOAD ON LIGHTING BRANCH CIRCUIT SWITCH |
| | LEGS ON DIMMERS AND VERIFY DIMMER LISTING AND MAX LOAD |
| | APPROVED FOR USE. NEC 110.3(B) |
| | |
| | 5) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS ARE REQUIRED |
| | FOR LOW VOLTAGE SYSTEMS SUCH AS BUT NOT LIMITED TO |
| | NETWORK, SECURITY, CCTV, & AUDIO/VIDEO. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |