| Plan Review Notes For Permit 14100384 |
| Permit Number |
14100384 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-15 13:53:41 | 1. PROVIDE PLAN THAT SHOWS EXISTING (E) AND NEW (N) AS | | | STATED ON SUBMITTED APPLICATION. | | | 2 .PLAN TO SHOW MAIN SWITCH EXISTING AND NEW LOCATION. | | | 3. PROVIDE SIZE OF MAIN SWITCH (AMPERES) AND SIZE OF | | | CONDUCTORS SUPPLYING POWER. | | | 4. PROVIDE GROUNDING ELECTRODE DETAIL. (PER N.E.C. | | | 250.53) | | | 5. PROVIDE SIZE OF CONDUCTORS AND LOCATION OF WIRING TO | | | BE REPLACED AS STATED ON APPLICATION. | | | 6. SHOW LOCATION OF SMOKE AND CARBON MONOXIDE DETECTORS | | | AS PER FBC R314 & R 315. |
|