| 2015-02-19 15:24:56 | 02/19/2015 | | | PROJECT: LOVELAND NEW RESIDENCE | | | PERMIT#: 14100378 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: APPROVED WITH EXCEPTION | | | | | | 1) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS | | | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT | | | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE | | | INTERRUPTED. NEC 110.9 | | | | | | 2) AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING | | | INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED | | | FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO | | | ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE | | | DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR | | | STRUCTURES. NEC 250.94. | | | | | | 3) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY | | | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS | | | REQUIRED FOR SWIMMING POOL, SECURITY, CCTV, | | | AUDIO/VIDEO, NETWORK, ETC... | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|