Plan Review Notes
Plan Review Notes For Permit 14100378
Permit Number 14100378
Review Stop P
Sequence Number 1
Notes
Date Text
2014-10-30 08:17:511) THE PLUMBING RISER HAS DRY VENTS FOR THE FIRST FLOOR
 SHOWER, THE SECOND FLOOR TUB, THE TOILET IN THE
 PLAYROOM, AND THE SHOWER IN THE STUDIO.DRY VENTS
 CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT ABOVE
 THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE. FL. BLDG.
 CODE, RESIDENTIAL, SEC.P3104.3.
 2) CLEANOUTS ARE REQD. IN THE BASE OF THE STACKS PER
 FBCR, SEC.P3005.2.6.
 3) SUBMIT A GAS RISER FOR THE GAS INSTALLATION AND
 SUBMIT MANUFACTURER SPECIFICATIONS /INSTALLATION
 INSTRUCTIONS FOR THE TANKLESS WATER HEATER AND THE GAS
 STOVE OR PLACE NOTE ON PLANS THAT GAS TO BE UNDER
 SEPARATE PERMIT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR