| Notes |
| Date |
Text |
| 2014-10-30 08:17:51 | 1) THE PLUMBING RISER HAS DRY VENTS FOR THE FIRST FLOOR | | | SHOWER, THE SECOND FLOOR TUB, THE TOILET IN THE | | | PLAYROOM, AND THE SHOWER IN THE STUDIO.DRY VENTS | | | CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT ABOVE | | | THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE. FL. BLDG. | | | CODE, RESIDENTIAL, SEC.P3104.3. | | | 2) CLEANOUTS ARE REQD. IN THE BASE OF THE STACKS PER | | | FBCR, SEC.P3005.2.6. | | | 3) SUBMIT A GAS RISER FOR THE GAS INSTALLATION AND | | | SUBMIT MANUFACTURER SPECIFICATIONS /INSTALLATION | | | INSTRUCTIONS FOR THE TANKLESS WATER HEATER AND THE GAS | | | STOVE OR PLACE NOTE ON PLANS THAT GAS TO BE UNDER | | | SEPARATE PERMIT. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|