| 2014-11-07 16:31:37 | 11/7/2014 |
| | PROJECT: LOVELAND NEW RESIDENCE |
| | PERMIT#: 14100378 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) REVISE ELECTRICAL RISER DIAGRAM TO INDICATE THE USE |
| | OF A METER ENCLOSURE APPROVED FOR THE PROPOSED LOAD TO |
| | BE SERVED AND TO IDENTIFY THE VOLTAGE AND AMPERE RATING |
| | EACH OF THE MAIN BREAKERS. |
| | |
| | 2) CLARIFICATION REQUIRED. PANEL "A" IS INDICATED WITH |
| | A 300AMP MAIN. THE RISER DIAGRAM INDICATES IT AS A |
| | 150AMP PANEL FED FROM AN UNIDENTIFIED MAIN. |
| | |
| | 3) CLARIFICATION REQUIRED. PANEL "B" IS INDICATED AS A |
| | 100AMP PANEL ON THE RISER DIAGRAM BUT AS A 150AMP PANEL |
| | ON THE PANEL SCHEDULE FED FROM AN UNIDENTIFIED SOURCE. |
| | . |
| | |
| | 4) PANEL SCHEDULE FOR PANEL "A" INDICATES A 15AMP |
| | BRANCH CIRCUIT FOR THE DINING RM. THE DINING ROOM IS A |
| | ROOM THAT IS REQUIRED TO BE SERVED FROM A 20AMP BRANCH |
| | CIRCUIT. NEC210.52 |
| | |
| | 5) REVISE PANEL SCHEDULES TO INDICATE EACH CIRCIUT |
| | SHALL BE LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, |
| | AND SPECIFIC PURPOSE OR USE. NEC 408.4 |
| | |
| | 6) CLARIFY THE USE AND PURPOSE OF THE SPECIAL AND |
| | GENERAL PURPOSE OUTLETS LOCATED IN THE FRONT FOYER COAT |
| | CLOSET. |
| | |
| | 7) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 |
| | |
| | 8) PROVIDE CIRCUIT NUMBERS ON THE FLOOR PLAN |
| | CORRESPONDING TO THE DESIGNATED CIRCUIT IN THE PANEL. |
| | |
| | 9) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| | |
| | 10) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | REQUIRED FOR SWIMMING POOL, SECURITY, CCTV, |
| | AUDIO/VIDEO, NETWORK, ETC... |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |