Plan Review Notes
Plan Review Notes For Permit 14100378
Permit Number 14100378
Review Stop B
Sequence Number 1
Notes
Date Text
2014-10-27 14:26:54NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY BUILDING (2300 N.
 JOG RD.) TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK
 COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES
 ARE DUE. REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE DRAINAGE PLAN. SEC. R401.3 OF 2010
 FBC-RESIDENTIAL.
  
 3- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF 2010
 FBC-RESIDENTIAL.
  
 4- DESIGNER OF RECORD TO PROVIDE SPECIFICATIONS ON
 PLANS SHOWING COMPLIANCE WITH UNVENTED ROOF VENTILATION
 SHOWN ON PLANS. SEC. R806.1 OF 2010 FBC-RESIDENTIAL.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ARCHED WOOD ENTRY DOOR SIZE AS SHOWN ON PLANS.
 (NOTE: NEED TO REVISE DOOR SIZE TO COMPLY WITH EGRESS).
 B) WINDOW MULLIONS. NOA 12-0308.37 SUBMITTED EXPIRED
 SEPTEMBER 16,2014. NEED CURRENT NOA.
 C) FIXED WINDOWS. NOA 13-0206.05 SUBMITTED EXPIRED JUNE
 17, 2014. NEED CURRENT NOA.
 D) FLAT ROOF MODIFIED BITUMEN ROOF SYSTEM NOA
 12-0716.18 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE.
 VISIT THE MIAMI-DADE WEBSITE DOWNLOAD CURRENT NOA AND
 RE-SUBMIT.
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR.
 OR, WRITE DOWN FLORIDA PRODUCT APPROVAL NUMBER AFTER
 EACH SPECIFIED CONNECTOR.
 F) PRECAST LINTELS AS SHOWN ON PLANS. AND, REVISE
 PRODUCT APPROVAL NUMBER SPECIFIED ON SHEET S.2. NOA
 12-0209.13 FROM FLORIDA PRODUCT APPROVAL FL 158 WAS
 SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS TO FBC.
  
 7- CLEARLY SPECIFY WHERE IS JELD-WEN DOOR FLORIDA
 PRODUCT APPROVAL FL15558 GOING TO BE INSTALLED. PLANS
 AND ELEVATIONS SUBMITTED DON'T SHOW THIS TYPE OF DOOR.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 8- FLAT ROOF PRODUCT APPROVAL: FROM REVISED NOA
 SUBMITTED (SEE COMMENT #5(D) ABOVE) CLEARLY IDENTIFY
 SPECIFIC APPROVED FLAT ROOF ASSEMBLY TO BE INSTALLED
 AND PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF THE
 NOA. NEED THE RAS 117 CALCULATIONS TO MEET THE DESIGN
 PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 9- A) MAIN HOUSE ENTRY DOOR SIZE DOESN'T COMPLY WITH
 SEC. R11.2 OF 2010 FBC-RESIDENTIAL. REVISE AS REQUIRED.
 NOTE:
 B) SAME COMMENT APPLIES TO THE REAR BUILDING: REVISE
 SIZE OF ENTRY DOOR FOR EACH STUDIO TO COMPLY WITH SEC.
 R311.2.
  
 10- WEST ENTRY ELEVATION ON SHEET S.2: PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR ARCHED ENTRY DOOR VENEER
 AND PC MOLDING SPECIFY MATERIAL AND THICKNESS AND
 FASTENING TO THE WALL. SEC. R301 OF 2010
 FBC-RESIDENTIAL.
  
 11- SHEET S.2:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 STAIR HANDRAILS SHOWING COMPLIANCE WITH THE LOADS OF
 TABLE R301.5 AND WITH SEC. R311.7.7 OF 2010
 FBC-RESIDENTIAL. SPECIFY LOCATION OF RAILINGS AND
 REVISE TYPICAL STAIR & GUARDRAIL NOTES ON SHEET S.2..
 REFER TO CORRECT CODE SECTIONS FROM THE
 FBC-RESIDENTIAL.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 MASTER BEDROOM BALCONY GUARDRAIL SYSTEM SHOWING
 COMPLIANCE WITH THE LOADS OF TABLE R301.5 AND WITH SEC.
 R312 OF 2010 FBC-RESIDENTIAL. REVISE TYPICAL STAIR &
 GUARDRAIL NOTES ON SHEET S.2.. REFER TO CORRECT CODE
 SECTIONS FROM THE FBC-RESIDENTIAL.
  
 12- SHEET S.6: MAIN HOUSE AND REAR BUILDING:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 ROOF DRAINAGE TO SHOW COMPLIANCE WITH SEC. R903.4 OF
 2010 FBC-RESIDENTIAL. SPECIFY SIZES OF SCUPPERS,
 DOWNSPOUTS, ETC . ALSO : NEED TO SHOW THEM ON THE
 EXTERIOR ELEVATIONS. ON SHEET S.2.. SEC. 107.2.1 OF
 CITY AMENDMENTS.
  
 B) SPECIFY OVERFLOW SCUPPERS SIZE AND LOCATION TO SHOW
 COMPLIANCE WITH SEC. R903.4.1 OF 2010 FBC-RESIDENTIAL.
  
 C) REVISE THE FIRST PRE-ENGINEERED WOOD TRUSSES NOTE.
 REFER TO CORRECT BUILDING CODE EDITION AND SECTION. THE
 BUILDING CODE IS 2010 NOT 2007.
  
 13- ALL WALL SECTIONS FOR MAIN HOUSE AND REAR BUILDING:
 A) SPECIFY STUCCO THICKNESS AS REQUIRED BY TABLE
 R702.1(1) OF 2010 FBC-RESIDENTIAL.
 B) SPECIFY THE TWO LAYERS OF APPROVED WATER RESISTANT
 BARRIER AS REQUIRED BY SEC. R703.6.3 OF 2010
 FBC-RESIDENTIAL.
 C) CLEARLY SPECIFY THE MINIMUM HEIGHT ABOVE FINISHED
 GRADE AS REQUIRED BY SEC. R404.1.6 AND SEC. R704 OF
 2010 FBC-RESIDENTIAL.
  
 14- ENERGY CALCULATIONS SUBMITTED:
 A) THERE ARE TWO SEPARATE BUILDINGS. PROVIDE ENERGY
 CALCULATIONS FOR EACH BUILDING. SEC. 103.2.1.1.2 OF
 2010 FBC-ENERGY CONSERVATION.
 B) REVISE THE AREA WEIGHTED AVERAGE OVERHANG DEPTH AND
 AREA WEIGHTED AVERAGE SPECIFIED IN ITEM #7. SEE PLANS
 AND REVISE AS REQUIRED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
 C) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION ON
 PAGE 3 OF 6. SEE PLANS FOR CORRECT INFORMATION. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
 D) BUILDER NAME ON TOP OF FORM IS INCORRECT. REVISE AS
 REQUIRED. SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY
 CONSERVATION.
 E) SEE MECHANICAL REVIEW COMMENTS AND COORDINATE
 COOLIING AND HEATING INFORMATION WITH REQUESTED REVISED
 A/C EQUIPMENT SIZING CALCULATIONS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
 F) ENGINER TO PROVIDE ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 471 FL. ST.
  
 15- PROVIDE WINDOW AND DOOR MANUFACTURER'S SPECS
 SHOWING COMPLIANCE WITH THE U-FACTOR AND SHGC FACTOR
 SPECIFIED IN THE ENERGY CALCULATIONS IN ITEM #7.
 SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 16- SHEET S.1:
 A) REVISE DESIGN CRITERIA ITEM #7. THIS IS NOT LEVEL OF
 ALTERATION: II. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
 B) REVISE THE STRUCTURAL NOTE "A". ROOF LOADS DON'T
 CORRESPOND TO TYPE OF ROOF ON THIS PROJECT. REVISE AS
 REQUIRED. SPECIFY PROPER LIVE AND DEAD LOADS. SEC. R301
 OF 2010 FBC- RESIDENTIAL.
 C) REVISE PROJECT DATA INFORMATION. A/C AREA 1ST LEVEL
 WAS REPEAT TWICE, INSTEAD OF SAYING 1ST AND 2ND FLOOR
 A/C AREA. SEC. 107.2.1 CITY AMENDMENTS.
  
 17- SECTION A-A ON SHEET S.5:
 A) CLARIFY SIZE OF STAIR TREADS. 11" OR 10". THERE ARE
 TWO DIFFERENT SPECS ON SAME DRAWING. SEC. R311.7.4.2 OF
 2010 FBC-RESIDENTIAL.
 B) PROVIDE SPECIFICATIONS FOR FIREBLOCKING IN ALL AREAS
 AS REQUIRED BY SEC. R302.11 OF 2010 FBC-RESIDENTIAL.
  
 18- SPECIFY CARBON MONOXIDE ALARM ON FIRST FLOOR
 BEDROOM/DEN ROOM. SEC. R315 OF 2010 FBC-RESIDENTIAL.
 (NOTE: THIS IS A BEDROOM ACCORDING TO THE DEFINITION ON
 THE 2010 FBC-ENERGY CONSERVATION).
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REMOVE AND REPLACE ALL REVISED DRAWINGS.
 *** PLEASE PROVIDE COMPLETE INFORMATION FOR THE POOL
 UNDER A SEPARATE PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]