| 2014-12-04 10:34:16 | 1) THE SINK NEXT TO THE 3 COMPARTMENT SINK IS MISSING |
| | FROM THE WATER RISER DIAGRAM. |
| | 2) AS DRAWN, THE SANITARY RISER SHOWS THE GREASE TRAP, |
| | MOP SINK, FLOOR SINKS, AND HAND SINKS ON A HORIZONTAL |
| | WET VENT WHICH IS PROHIBITED BY THE 2010 FL. PLUMBING |
| | CODE (FPC) SEC.909. A VENT DRAWN ON THE WATER CLSET IS |
| | AN OPTION TO CORRECT THIS VIOLATION. 2ND REQUEST. |
| | 3) SUBMIT MANUF.SPECS/INSTALLATION INSTRUCTIONS FOR THE |
| | GELATO MACHINE.WPB AMEND TO 2010 FBC SEC.107.2.1. 2ND |
| | REQUEST. |
| | 4) SUBMIT DETAILS OF THE GREASE INTERCEPTOR. IF THE |
| | INTERCEPTOR IS CONCRETE, THE DESIGN SHALL COMPLY WITH |
| | THE 2010 FPC SECS. 1003.5.2, 1003.5.3, AND THE FLORIDA |
| | ADMINISTRATIVE CODE RULE 64E-6. SUBMIT A DETAIL FOR THE |
| | INTERCEPTOR. 2ND REQUEST.WPB AMEND. TO 2010 FPC SEC. |
| | 107.2.1. 2ND REQUEST. |
| | 5) SHT. A-6 - THE GREASE INTERCEPTOR CALCULATIONS |
| | INDICATE 17 SEATS BUT THE PLAN ONLY SHOWS 8. CLARIFY. |
| | 2ND REQUEST. |
| | 6) YOU HAVE PROVIDED CALCULATIONS FOR THE GPM |
| | DISCHARGING INTO THE INTERCEPTOR. IN ORDER TO FIGURE |
| | THE TOTAL GPM DISCHARGING INTO THE INTERCEPTOR, ALL THE |
| | FIXTURES DISCHARGING INTO THE INTERCEPTOR MUST BE |
| | INCLUDED IN THE CALCULATIONS.YOU HAVE NOT INCLUDED THE |
| | THREE HAND SINKS. CLARIFY. |
| | 7) A FULL FLOW VALVE IS REQD.ON THE C.W.FEED TO THE |
| | WATER HEATER. 2010 FPC SEC.606.1. |
| | |