| Date |
Text |
| 2014-10-23 11:00:19 | 1) THE PLANS SHOW THE RESTROOMS LOCATED IN AN AREA THAT |
| | REQUIRES ACCESS THROUGH THE FOOD PREPARATION AREA.THE |
| | ROUTE TO PUBLIC TOILET FACILITIES REQUIRED BY SEC.403.3 |
| | OF THE FLORIDA PLUMBING CODE SHALL NOT PASS THROUGH |
| | KITCHENS, STORAGE ROOMS OR CLOSETS PER SEC.403.3.1. |
| | 2) SUBMIT MANUF. SPECIFICATIONS FOR THE GELATO MACHINE. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 3) SUBMIT A LAYOUT OF THE EXISTING FLOOR PLAN. WPB |
| | AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 4) SHT. A-3 - THE PLANS REFERENCE THE 2007 FLORIDA |
| | BUILDING CODE. THE CODE IN EFFECT IS THE 2010 FBC. |
| | THERE IS NO CHAPTER 11 IN THE 2010 FBC AND THE FIGURE |
| | NUMBERS LISTED IN THE DETAILS DO NOT EXIST IN THE 2010 |
| | ACCESIBILITY CODE. |
| | 5) SHT. A-5 - DETAIL #3 - PLUMBING FIXTURE MOUNTING |
| | HEIGHTS - THE WATER CLOSET SHALL BE 16"-18" TO THE |
| | CENTERLINE FROM ANY SIDE WALL OR PARTITION. FAC |
| | SEC.604.2. |
| | 6) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. WPB AMEND. |
| | TO 2010 FBC SEC.107.3.5.1.3. |
| | 7) AS DRAWN, THE SANITARY RISER HAS THE GREASE TRAP AND |
| | ALL THE OTHER GREASE WASTE FIXTURES ON A WET VENT WHICH |
| | DOES NOT COMPLY W/ 2010 FPC SEC.909. |
| | 8) CLEANOUTS ARE REQUIRED ON ALL STACKS PER THE 2010 |
| | FPC SEC.708.3.4. |
| | 9) SHT. A-6 - THE GREASE INTERCEPTOR CALCULATIONS |
| | INDICATE 27 SEATS BUT THE PLAN ONLY SHOWS 8. SUBMIT A |
| | FULL SEATING PLAN FOR REVIEW. WPB AMEND. TO 2010 FBC |
| | SEC. 107.2.1. |
| | 10) THE SINK AT THE VESTIBULE SHALL COMPLY W/ THE |
| | FLORIDA ACCESSIBILITY CODE SEC. 212 & 606. |
| | 11) SUBMIT SPECIFICATIONS FOR THE GREASE TRAP.WPB |
| | AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 12) SHOW THE DIMENSIONS OF THE TOILET ROOM NEAR THE |
| | PREP AREA. WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |