| 2014-10-17 16:37:53 | 600 OKEECHOBEE BOULEVARD | | | TRACKING #14100358 | | | PERMIT #14090274 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | NO ADDRESS PROVIDED IN TITLEBLOCK INFORMATION. | | | | | | NO AUTOMATIC TRANSFER SWITCH PROVIDED WITH FIRE PUMP | | | CONTROLLER. | | | | | | NO JOCKEP PUMP OR CONTROLLER PROVIDED TO PREVENT FIRE | | | PUMP FROM CYCLING ON/OFF. | | | | | | WHERE IS THE SECONDARY POWER SUPPLY TO THE FIRE PUMP | | | AND CONTROLLERS? | | | | | | HOW WILL THE FIRE PUMP CONDUCTORS BE PROTECTED? | | | CONCRETE ENCASEMENT? | | | | | | FIRE PUMP, CONTROLLERS AND EQUIPMENT INSTALLATION WILL | | | NEED TO COMPLY WITH NFPA 20 (DRAINAGE, LIGHTING, | | | EMERGENCY LIGHTING, FIRE-RATED ENCLOSURE) AND BE | | | INSPECTED, TESTED AND APPROVED WITH THE FIRE DEPARTMENT | | | PRIOR TO PERMANENT OR TEMPORARY USAGE. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|