| Plan Review Notes For Permit 14100358 |
| Permit Number |
14100358 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-23 13:42:43 | 14100358 | | | 600 OKEECHOBEE BLVD. | | | TEMPORARY SERVICE REVISION | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | SHOW LOCATION ON SITE PLAN FOR THE FIRE PUMP AND | | | FEEDERS. VERIFY THAT ALL FEEDERS ARE RATED AT 125% OF | | | THE FULL LOAD CURRENTS. NEC 695.6 | | | | | | PROVIDE SPECIFICATIONS ON THE FIRE PUMP CONTROLLER AND | | | DISCONNECT. VERIFY THAT THE FIRE PUMP MAIN DISCONNECT | | | IS SERVICE RATED. NEC 695.4 | | | | | | VERIFY THAT SERVICE AND CIRCUIT CONDUCTORS ARE | | | PROTECTED. NEC 695.6 | | | | | | VERIFY THAT THE DISCONNECTING MEANS IS MARKED AND | | | SUPERVISED IN THE CLOSED POSITON OR LOCKED IN THE | | | CLOSED POSITION. NEC 695.4 | | | | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | [email protected] | | | | | | | | | |
|