Plan Review Notes
Plan Review Notes For Permit 14100358
Permit Number 14100358
Review Stop E
Sequence Number 1
Notes
Date Text
2014-10-23 13:42:4314100358
 600 OKEECHOBEE BLVD.
 TEMPORARY SERVICE REVISION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 SHOW LOCATION ON SITE PLAN FOR THE FIRE PUMP AND
 FEEDERS. VERIFY THAT ALL FEEDERS ARE RATED AT 125% OF
 THE FULL LOAD CURRENTS. NEC 695.6
  
 PROVIDE SPECIFICATIONS ON THE FIRE PUMP CONTROLLER AND
 DISCONNECT. VERIFY THAT THE FIRE PUMP MAIN DISCONNECT
 IS SERVICE RATED. NEC 695.4
  
 VERIFY THAT SERVICE AND CIRCUIT CONDUCTORS ARE
 PROTECTED. NEC 695.6
  
 VERIFY THAT THE DISCONNECTING MEANS IS MARKED AND
 SUPERVISED IN THE CLOSED POSITON OR LOCKED IN THE
 CLOSED POSITION. NEC 695.4
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW