Plan Review Notes
Plan Review Notes For Permit 14100350
Permit Number 14100350
Review Stop P
Sequence Number 1
Notes
Date Text
2014-10-30 08:53:211) SUBMIT DRAWINGS FOR THE PNEEUMATIC TUBE SYSTEM AT
 THE DRIVE THROUGH IF THAT IS BEING REPLACED. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 2) SHT. A-3 - THERE ARE VTR'S THAT APPEAR TO BE WITHIN
 10 FT. OF THE ROOF TOP UNITS AC-1, AC-2, AC-3. IF THE
 UNITS HAVE INTAKE/MAKEUP AIR CAPABILITIES THE VENTS
 SHALL COMPLY W/ 2010 FPC SEC.904.5.
 3) SHT. P-3 - THE CONDENSATE DRAINS CANNOT DISCHARGE TO
 THE SANITARY SYSTYM PER CITY ORD. SEC. 90-126.
 4) CLEAR WATER WASTE 9CONDENSATE) SHALL NOT DISCHARGE
 TO THE GREASY WASTE SYSTEM PER THE 2010 FPC SEC.1003.2.
 5) SIZE THE HOT AND COLD WATER LINES TO THE EMPLOYEE
 RESTROOM FIXTURES. THE JANITOR SINK IS NOT SHOWN ON THE
 WATER RISER. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 6) SUBMIT MANUF. SPECIFICATIONS/INSTALLATION
 INSTRUCTIONS FOR TANKLESS WATER HEATER. WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 7) SUBMIT A GAS RISER DIAGRAM FOR ANY CHANGES TO THE
 GAS SYSTEM.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 INDICATE ON SHT.P-4 IF THE LP GAS TANK & PIPING IS NEW
 OR EXISTING. IF NEW, SUBMIT A GAS RISER FOR THIS
 INSTALLATION.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  