| Plan Review Notes For Permit 14100350 |
| Permit Number |
14100350 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-28 09:20:04 | PASS PROVISO | | | | | | 1) REFER TO SECTION 606.3 INSTALLATION (ACCESS DOORS | | | FOR DUCT DETECTORS) 2010 FBC (M) | | | | | | 2) HOODS, FIRE SUPPRESSION AND REFRIGERATION | | | ARE NOT INCLUDED IN THIS REVIEW. SEPARATE | | | APPLICATION, PLAN AND PERMITS REQUIRED. | | | PER SECTION 107 FBC 2010 | | | 3) PROVIDE AUTOMATIC DAMPERS ON | | | OUTDOOR AIR AND EXHAUST. PER | | | SECTION 503.2.4.4 SHUTOFF DAMPER | | | CONTROLS 2010 FLORIDA ENERGY CODE. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|