Plan Review Notes
Plan Review Notes For Permit 14100350
Permit Number 14100350
Review Stop M
Sequence Number 1
Notes
Date Text
2014-10-28 09:20:04PASS PROVISO
  
 1) REFER TO SECTION 606.3 INSTALLATION (ACCESS DOORS
 FOR DUCT DETECTORS) 2010 FBC (M)
  
 2) HOODS, FIRE SUPPRESSION AND REFRIGERATION
 ARE NOT INCLUDED IN THIS REVIEW. SEPARATE
 APPLICATION, PLAN AND PERMITS REQUIRED.
 PER SECTION 107 FBC 2010
 3) PROVIDE AUTOMATIC DAMPERS ON
 OUTDOOR AIR AND EXHAUST. PER
 SECTION 503.2.4.4 SHUTOFF DAMPER
 CONTROLS 2010 FLORIDA ENERGY CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676